Product overview
Single-pole DIN-rail AC Type 2 surge protective device with 385 V AC Uc, 160 kA Imax and 80 kA In, as marked on the pictured model.

Technical specifications
| Model | TZG40-160 |
|---|---|
| Offered configuration | 1P, Type 2 AC SPD |
| Maximum continuous voltage Uc | 385 V AC |
| Maximum discharge current Imax | 160 kA (8/20 μs) |
| Nominal discharge current In | 80 kA (8/20 μs) |
| Voltage protection level Up | ≤2.5 kV |
| Mounting | 35 mm DIN rail |
| Standard marked on product | IEC/EN 61643-11 |
| Normal ambient temperature | -5 to +40 °C |
| Maximum elevation | 2,000 m |
Offered configuration
The photographed TZG40-160 is the 1P, 385 V AC, Type 2 version. The supplier’s series artwork also lists other voltage and current configurations. The technical table above applies to the pictured 160 kA version.
Mounting and connections
The drawings show a 35 mm DIN rail, 98 mm height and approximately 67 mm depth. Follow the terminal markings and match the line and protective earth connections to the installation design.
Operating conditions
The supplier gives a normal ambient range of -5 to +40 °C and elevation up to 2,000 m. Check upstream protection and coordination against the electrical installation requirements.