NewTrend · Extended multifunction timer relay
Product overview
NewTrend RT8-N2 provides ten extended timing modes in an 18mm DIN-rail housing. In addition to power-on on-delay and interval operation, it offers S-triggered delay, accumulated timing, repeat cycling, timing on both S edges and a delayed 1-second pulse. Rotary selectors and a fine-adjustment potentiometer set the function and timing interval. The relay has 2 SPDT contacts rated 16A AC-1.
Technical selection summary
| Model | RT8-N2 |
|---|---|
| Output contacts | 2 SPDT |
| A230 power input | AC maximum 6VA / 1.9W |
| Weight | W240: 82g; A230: 81g |
| Function | A, As, Aw, B, Bs, Bw, Cs, Ds, Fe, Js |
| Supply terminals | A1-A2 |
| Control supply options | W240: AC/DC 12-240V; A230: AC 230V; 50-60Hz |
| Supply tolerance | -15% to +10% |
| W240 burden | AC 0.09-3VA / DC 0.05-1.7W |
| Supply indication | Green LED |
| Time setting | Range selector and 10%-100% potentiometer |
| Adjustment range | 0.1s-10days; ON; OFF |
| Marked time ranges | 1s, 10s, 1min, 10min, 1h, 10h, 1day, 10days; ON and OFF positions |
| Time setting deviation | 10% with mechanical adjustment |
| Repeat accuracy | 0.2% of set value |
| Temperature coefficient | 0.05%/degree C at 20 degrees C |
| Contact rating | 16A, AC-1 |
| Switching voltage | 250VAC / 24VDC |
| Minimum DC breaking power | 500mW |
| Output indication | Red LED |
| Mechanical life | 10,000,000 operations |
| Electrical life (AC-1) | 100,000 operations |
| Reset time | Maximum 200ms |
| Operating temperature | -20 to +55 degrees C |
| Storage temperature | -35 to +75 degrees C |
| Mounting | DIN rail to EN/IEC 60715 |
| Protection | IP40 front panel; IP20 terminals |
| Operating position | Any |
| Overvoltage category | III |
| Pollution degree | 2 |
| Maximum conductor size | Solid: 1 x 2.5mm2 or 2 x 1.5mm2; with sleeve: 1 x 2.5mm2 (AWG 12) |
| Terminal tightening torque | 0.4Nm |
| Body dimensions | 90 x 18 x 64mm |
| Referenced standards | EN 61812-1; IEC 60947-5-1 |
Choose the exact function code from the timing chart. Accumulated timing, retriggering and the Js 1-second pulse have different behavior from the standard multifunction series.
Operation
- Power-on modes A and B provide on-delay and timed-interval operation. The remaining modes use the S input for the illustrated triggered, accumulated, cycling or edge-controlled sequence.
- Js delivers a 1-second output pulse after the selected delay. Use the waveform chart to specify the trigger and retrigger behavior.
Typical applications
- Lighting and heating control
- Motor, pump and fan control circuits
- Equipment sequencing requiring selectable timing or latching operation
Specify your enquiry
For a focused quotation, include:
- Control supply: AC/DC 12-240V or AC 230V
- Function code, timing interval and S-input trigger pattern
- Load characteristics, quantity and delivery destination
Download NewTrend RT8-N2 datasheet (PDF)
Product reference images and drawings
Supply, trigger and contact connections
Ten extended operating functions
Common housing dimensions; RT8-N1 front view shown.
Delay time equals the selected range multiplied by the 10%-100% fine adjustment. Match the S-input wiring and function code to the required sequence. ON and OFF provide permanent output states. Installation and wiring must be performed by qualified electricians.