NewTrend · MC1-63
Product overview
MC1-63 compact contactors provide DIN-rail load switching in a single-module-width housing. Select the supported current, main-contact arrangement and the photographed AC 230V coil version.
Technical selection summary
| Current range | 40A, 63A. |
|---|---|
| Contact configurations | 1NO, 1NC. |
| Main circuit | 250V AC, 50/60Hz. |
| Coil selected here | AC 230V; other coil versions are subject to exact-model confirmation. |
| Insulation / impulse withstand | Ui 500V AC; Uimp 2.5kV, with the source noting 4kV for 12/24/48V AC variants. |
| Mechanical / electrical endurance | 1,000,000 / 100,000 cycles. |
| Maximum switching operations | 100 per day. |
| Protection | IP20 device; IP40 in a suitable modular enclosure. |
| Ambient | Operating -5 to +60 C; storage -40 to +70 C. |
| Spacing | Provide the specified spacer between adjacent contactors in an enclosure at 50-60 C. |
| Dimensions | 18mm width, 92mm overall height and 67mm depth; see the applicable drawing. |
Series reference image. The supplied rating, contact arrangement and coil voltage must match the selected configuration; motor loads require utilization-category selection rather than the resistive-current value.
Typical applications
- Lighting and resistive-heating control in building distribution boards.
- Ventilation, pumps and small motors when selected for the actual utilization category.
Specify your enquiry
For a focused quotation, include:
- Rated current and load type, including motor starting duty where relevant.
- Pole count, NO/NC contact arrangement and coil voltage with AC/DC designation.
- Quantity, installation conditions and any approval requirements.