NewTrend · CH8
Product overview
CH8 modular AC contactors switch building lighting, heating and other distribution-board loads. This page groups the 2P all-NO versions with 25A, 63A and 100A ratings.
Technical selection summary
| Model | CH8 |
|---|---|
| Poles | 2P |
| Rated current (AC-7a) | 25A / 63A / 100A |
| Main contacts | 2NO |
| Rated operating voltage (Ue) | 250V AC |
| Rated insulation voltage (Ui) | 500V AC |
| Coil voltage | AC 24V / 110V / 230V / 240V |
| Frequency | 50/60Hz |
| Load category | AC-7a / AC-7b |
| Mechanical endurance | 2,000,000 cycles |
| Electrical endurance | 100,000 cycles |
| Operating temperature | -5°C to +60°C |
| Mounting | 35mm DIN rail |
| Reference standards | IEC/EN 61095; IEC 60947-4-1 |
Typical applications
- Lighting and resistive-heating control in building distribution boards.
- Ventilation, pumps and small motors when selected for the actual utilization category.