NewTrend · High-current PV DC Isolation
Product overview
H-800 is a non-polar, two-pole DC switch disconnector for built-in installation in photovoltaic inverters and DC equipment. The available configuration on this page is 630A / DC-PV2 at 1000V or 1500V DC. Standard, A and B front-operation versions and the A1 side-operation version are matched to their documented model codes and dimension drawings.
Key features
- Two-pole design for 1000–1500V DC switching; the source describes 500–750V DC per pole.
- DC arc-extinguishing design for load switching and safe circuit isolation.
- Visible contact-position indication for checking the operating state.
- Opening and closing operation is independent of the operator’s switching speed.
- Lockable handle, compact construction and modular assembly options.
- IP66 operator-side protection when panel-mounted; switch terminals are IP20.
- Operating range −40°C to +85°C; the source page describes no derating up to 60°C.
Technical specifications — 630A / DC-PV2
Electrical Characteristics
| Rated Working Voltage (Ue) | 1000V / 1500V DC |
|---|---|
| Rated Current (Ie) | 630A |
| Rated Impulse Withstand Voltage (Uimp) | 12kV |
| Rated Short-Time Withstand Current, 1 s (Icw) | 10kA |
| Rated Short-Circuit Making Capacity (Icm) | 10kA |
| Contact Resistance | <0.5mΩ |
Installation Environment
| Utilization Category DC | DC-PV2 |
|---|---|
| Number of cycles of operation(With current) | 200 |
| Number of cycles of operation(Without current) | 5,000 |
| Poles | 2 |
| Mounting | Base Screws Mounting |
| Screw for Mounting (M5) | 2.0–3.0 N·m |
| Wiring Screw (M14) | According to IEC 60947-1, 20 N·m |
| Ambient temperature allowed between | −40°C to +85°C |
| Storage temperature allowed between | −40°C to +85°C |
| Relative Humidity | 90% |
| Pollution Degree | 3 |
| IP rating terminals | IP20 |
| Outside the ark handle | IP66 |
Selection and installation references
| Standards | IEC/EN 60947-3; AS 60947.3; GB/T 14048.3 |
|---|---|
| Available rated current / utilization category | 630A / DC-PV2 |
| Current-carrying operating cycles | 200 |
| Mechanical operating cycles | 5000 |
| Wiring graph scope | One string; the source wiring graph lists one pole in series. Follow the complete two-pole connection diagram. |
| 630A conductor reference | 2 × 185mm² copper conductor, or equivalent copper busbar, as specified in the source installation table |
| Standard coupling shaft total length | 182mm |
| Minimum coupling shaft total length | 80mm |
| Customizable distance in the dimension drawing | 27–300mm; refer to the model-specific drawing and confirm shaft/coupling requirements |
| Auxiliary contact | Optional; required contact configuration and complete ordering suffix: To be confirmed |
| Source certification references | CE / CB / TUV / RCM / RoHS; supplied-marking applicability: To be confirmed |
Model and operation arrangement
| Model | Operation arrangement | Rated current / category | Rated voltage |
|---|---|---|---|
| H-800-2P | Front / standard | 630A / DC-PV2 | 1000V / 1500V DC |
| H-800-2P-A | Front / A | 630A / DC-PV2 | 1000V / 1500V DC |
| H-800-2P-B | Front / B | 630A / DC-PV2 | 1000V / 1500V DC |
| H-800-2P-A1 | Side / A1 | 630A / DC-PV2 | 1000V / 1500V DC |
The standard version uses the current factory product-page main image. A, B and A1 views are the corresponding real structure illustrations from the directly linked family PDF; their original illustration detail is retained. The optional auxiliary contact and full ordering suffix must be confirmed for the required assembly.
Applications
PV inverter and DC equipment isolation within the selected voltage and current rating. The switch provides two-pole switching for one DC circuit. Panel installation is required for the stated operator-side IP66 protection; exposed switch terminals remain IP20.
Application reference illustration from the selected source page. Model applicability: To be confirmed.
Supplied and optional accessories
The family document lists the handle, standard 182mm coupling square shaft, interphase barrier, M14 binding kits and specification sheet as the standard configuration. Auxiliary contacts and a coupling shaft of a specified custom length are optional. Confirm the required assembly, auxiliary contact and shaft dimensions for the order.
Installation requirements
Use copper conductors or an equivalent copper busbar and the documented conductor section. Prepare connections so that only conductive parts are clamped, and tighten every connection, including bridging links, to the specified torque before energization. Base mounting uses M5 screws at 2.0–3.0N·m; M14 wiring connections use 20N·m according to IEC 60947-1.
Download the complete H-800 family datasheet (3 PDF pages / 6 printed pages)
The complete family reference includes additional 800A/DC-PV1 material. The available configurations on this page are the 630A/DC-PV2 versions; use the selected model-specific drawings and the confirmed ratings above.
Wiring and structure selection
H-800 family reference; current selection on this page is 630A / DC-PV2. The full source diagram also includes 800A reference ratings.
H-800-2P dimensions
H-800-2P standard front-operation version. Dimensions in mm.
H-800-2P-A dimensions
H-800-2P-A front-operation version. Dimensions in mm.
H-800-2P-B dimensions
H-800-2P-B front-operation version. Dimensions in mm.
H-800-2P-A1 dimensions
H-800-2P-A1 side-operation version. Dimensions in mm.
Switch and accessory reference
H-800 family handle, shaft, interphase barriers, M14 kits and optional auxiliary-contact references.
Copper conductor and connection reference
Use the 630A column for the available configuration. The adjacent 800A column is retained only as full family reference.