CHINT · Air circuit breaker
Product overview
This CHINT NXA20N20 listing is for 3-pole, 2000 A air circuit breakers with an M-type controller. MD3 identifies draw-out installation and MF3 identifies fixed installation; select the full control-voltage and accessory suffix.
Technical selection summary
| Manufacturer models | NXA20N20-MD3 / NXA20N20-MF3 |
|---|---|
| Frame / rated current | 2000 A frame; 2000 A rated current on this page |
| Pole scope | 3P; no other pole/current combination is offered by this selection |
| Controller / installation | M-type basic protection; D = draw-out, F = fixed. Motor/manual operation is a separate full-code requirement |
| Main-circuit reference | AC 380/400/415 V or 440/525/690 V, 50/60 Hz; use the exact voltage duty |
| N breaking-capacity reference | Icu 80 kA at 380/400/415 V; 50 kA at 440/525/690 V in the matched N-frame column |
| Control supply | AC 220/230/240 V or AC 380/400/415 V catalogue order groups; separate from main-circuit voltage |
| Documents / installation | IEC/EN 60947-2; verify controller settings, busbar terminals and the fixed/draw-out installation drawing |
The old 800–6300 A family range does not describe this specific product. Do not substitute another frame, N/S/H breaking version, pole count or controller by changing an isolated option. Specify motor/manual operation, UVT, auxiliary contacts and complete control voltage before supply.
Typical applications
- Low-voltage main distribution switchgear
- Replacement of the exact frame, pole and controller construction
Product reference images and drawings
Match the exact model, construction and supplied revision. Family reference pages can show other ratings or versions.