NewTrend · LW26-20 YH5/3
Product overview
NewTrend LW26-20 YH5/3 three-level, seven-position voltmeter selector. Its programme selects three line and three phase-to-neutral voltages plus off.
Technical selection summary
| Parameter | Specification |
|---|---|
| Function | Voltmeter selection in a three-phase four-wire circuit |
| Programme | YH5/3-66 source programme; seven positionsCA,BC,AB,0,A,B,C |
| Measurement | Three line-to-line and three line-to-neutral readings with an off position |
| Current category | 20A source thermal-current size; not a20A motor-reversing rating |
| Circuit reference | AC230/400V50Hz; Ui690V reference |
| Panel mounting | Square48 x48mm front; source36 x36mm fixing centres; exact outline retained |
| Source module length | 22+9.6n mm, n=number of modules; source programme has3 levels |
| Installation | Use the actual YH5/3 continuity chart and voltmeter connection, not neighbouring motor/ammeter programmes |
Only YH5/3 is offered here. The retained source includes neighbouring programmes for reference; they are not interchangeable. Do not treat three levels as proof of a generic three-pole power-transfer switch.
Typical applications
- Three-phase four-wire panel voltmeter selection
Open technical reference image