DELIXI ELECTRIC · Self-resetting voltage protector
Product overview
The DELIXI DZ47sGQF protects low-voltage distribution circuits against sustained overvoltage and undervoltage and reconnects after the voltage recovers and the reset delay expires. The GQF version uses a top-in, bottom-out connection. Choose the current rating with the correct 1P+N or 3P+N configuration.
Technical selection summary
| Brand and series | DELIXI ELECTRIC DZ47sGQF |
|---|---|
| Product type | Self-resetting overvoltage and undervoltage protector |
| 1P+N reference | AC 230 V; 20, 25, 32, 40, 50 or 63 A |
| 3P+N reference | AC 400 V; 32, 40, 50, 63, 80 or 100 A |
| Frequency and standard | 50 Hz; JB/T 12762-2015 |
| Overvoltage threshold (L–N) | AC 275 ± 5 V; recovery at ≤ 253 V |
| Undervoltage threshold (L–N) | AC 160 ± 5 V; recovery at ≥ 195 V |
| Undervoltage trip time | 0.6–1.5 s |
| Automatic reset delay | 25 ± 5 s |
| Rated conditional short-circuit current reference | 6 kA; coordinate with the required circuit protection |
| Impulse withstand Uimp | 4 kV |
| Connection direction | DZ47sGQF: top supply / bottom load. DZ47sGQR is the separate bottom-supply version. |
| Mounting and protection | 35 mm DIN rail; IP20 body / IP40 when installed in a distribution box |
| Terminal capacity and torque | 1P+N: up to 25 mm², 2.5 N·m. 3P+N: up to 35 mm², 3.5 N·m. |
This voltage protector must be coordinated with the installation’s overcurrent and short-circuit protection. GQF and GQR have different supply directions. The manufacturer announced marking and neutral-position changes in December 2023; confirm the actual L/N markings, wiring diagram and production version before installation.
Typical applications
- Low-voltage distribution circuits requiring sustained overvoltage and undervoltage protection
- Terminal distribution boards using the matching single-phase or three-phase-plus-neutral version