DELIXI ELECTRIC · CDQ1F
Product overview
DELIXI CDQ1F transfers a load between two supplies using a load-disconnector mechanism and an intelligent controller. Select its linked frame/current, poles, positions, controller and documented duty version.
Technical selection summary
| Frames / currents | 63, 125, 250, 630, 800, 1250 and1600AF; exact frame-specific6–1600A settings are linked |
|---|---|
| Poles / positions | 2P up to630AF; 3P/4P throughout; 1600AF isIII-position only |
| Controllers | A:dial; B:LED; C:LCD with RS485; features depend on controller andII/III mechanism |
| Utilization category | Standard:AC-33B at63–800AF, AC-33iB at1250/1600AF; H:AC-33A at63/125AF or AC-33iA at250–800AF |
| Circuit / control | AC400V family; AC220V controller; match pole and neutral-sampling wiring to the exact installation diagram |
| Protection boundary | PC-class transfer equipment has no built-in overload/short-circuit trip; coordinate external protection |
| Reference / dimensions | 2023 current catalogue plus2026II-position instructions; controller and position-specific outlines supplied |
II has two connected positions; III adds the dual-off position. Fire dual-off functions require theIII mechanism. The displayed reference identifies the selected configuration; confirm the complete factory suffix and wiring with the quotation.
Typical applications
- DELIXI CDQ1F transfers a load between two supplies using a load-disconnector mechanism and an intelligent controller.