DELIXI · Visible-break AC switch disconnector
Product overview
The DELIXI CDH3 visible-break switch disconnector is used to isolate low-voltage distribution circuits. Its operating arrangement provides visible contact separation and a locking clip to help prevent accidental closing during maintenance. The illustrated CDH3-63 unit is marked 63 A, 230 V and 50 Hz.
Technical selection summary
| Model family | CDH3 |
|---|---|
| Rated frequency | 50 Hz |
| Rated operating voltage | 1P: AC 230 V; 2P / 3P / 4P: AC 400 V |
| Pole configurations | 1P, 2P, 3P and 4P |
| 63 A frame rated currents | 32 A and 63 A |
| 125 A frame rated currents | 100 A and 125 A |
| Utilization category | AC-22A |
| Rated impulse withstand voltage | 4 kV |
| Rated short-time withstand current | 12 × Ie for 1 s |
| Ambient conditions | −5 °C to +40 °C; altitude up to 2000 m |
| Ingress protection and mounting | IP20; TH35-7.5 mounting rail |
| Standards | IEC 60947-3; GB 14048.3 |
Keep the frame and rated current paired: 32/63 A belong to the 63 A frame, while 100/125 A belong to the 125 A frame. Follow the manufacturer isolation and locking procedure; this device is not an automatic overcurrent protective circuit breaker.
Typical applications
- Visible isolation in distribution and metering circuits.
- Maintenance isolation with the manufacturer locking arrangement.