CNC Electric · YC9VA
Product overview
The CNC Electric YC9VA is a single-phase voltage and current protection relay with separate digital voltage and current displays. The original manufacturer catalogue and instructions support an adjustable current threshold of 1–63A, nominal AC230V supply and adjustable overvoltage, undervoltage and reconnection-delay settings.
Technical selection summary
| Manufacturer model | YC9VA, as printed on the original factory product photographs |
|---|---|
| Rated supply / frequency | AC230V / 50–60Hz |
| Maximum-current threshold adjustment | 1–63A; this listing does not offer an 80A version |
| Overvoltage threshold range | 230–300V |
| Undervoltage threshold range | 110–210V |
| Switch-on / reconnection delay | 1–90s; catalogue describes a default 30s restart delay |
| Overvoltage action time | 0.1s below 275V; 0.02s at or above 275V, catalogue conditions |
| Undervoltage action time | 0.5s at or above 160V; <0.1s below 160V, catalogue conditions |
| Overcurrent trip delay | 1–90s within the catalogue timed region; 0.1s at/above its maximum-current condition |
| Voltmeter accuracy | ≤1% |
| Output contact / rated insulation voltage | 1NO / 400V |
| Protection / pollution degree | IP20 / 3 |
| Electrical / mechanical life | 100,000 / 1,000,000 operations |
| Operating temperature / altitude | −5°C to +40°C / ≤2,000m |
| Relative humidity / storage temperature | 50% at +40°C, non-condensing / −40°C to +55°C |
| Mounting / dimensions | 35mm DIN rail / 53mm width × 82mm height × 68mm depth |
| Photographed terminal arrangement | Bottom IN and top OUT; neutral terminals marked N |
Selection and installation
Observe the IN, OUT and N markings on the actual unit. The factory gallery labels the photographed bottom-input/top-output device YC9VA, while the shared catalogue labels that terminal-layout drawing YC9VA2; use the matching bottom-input diagram rather than the different three-terminal YC9VA layout. The catalogue and user instructions agree on a 1–63A current-setting range, which governs this page; a different 80A value on the web page is not adopted. This is a single-phase relay and is not the three-phase YC9VA-3. Retain correctly sized upstream short-circuit and overload protection. A monitoring relay is not a substitute for a circuit breaker or residual-current protection.
Typical applications
Single-phase residential, commercial and control distribution circuits requiring adjustable voltage monitoring, current monitoring and delayed automatic reconnection after supply recovery.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.