CNC Electric · YCB9-80M
Product overview
The CNC Electric YCB9-80M is a thermal-magnetic miniature circuit breaker for overload and short-circuit protection of AC distribution circuits. This page covers the original photographed three-pole C63 configuration: 63A, 400V AC, 50Hz and 6kA under IEC 60898-1. The M version is kept separate from the 10kA H version.
Technical selection summary
| Manufacturer model | YCB9-80M |
|---|---|
| Published configuration | 3P, 63A, C curve (C63) |
| Rated operating voltage / frequency | 400V AC / 50Hz, original product marking |
| Rated short-circuit capacity Icn | 6,000A under IEC/EN 60898-1; M version |
| Protection functions | Thermal overload, magnetic short-circuit protection and isolation |
| Standard marked on the product | IEC 60898-1 |
| Family standards in the current catalogue | IEC/EN 60898-1 and IEC/EN 60947-2; use the applicable standard and rating |
| Rated insulation voltage Ui | 500V, current manufacturer catalogue |
| Rated impulse withstand voltage Uimp | 4kV, current manufacturer catalogue |
| Instantaneous characteristic under IEC/EN 60898-1 | C curve: 5–10 times rated current; see original curve and test table |
| Mechanical / electrical life | 20,000 / 10,000 operations, current catalogue |
| Protection / pollution degree | IP20 / 2 |
| Reference ambient temperature | 30°C |
| Operating temperature | −5°C to +40°C; 24-hour average ≤35°C |
| Relative humidity | ≤50% at +40°C; higher humidity permitted at lower temperature |
| Installation altitude | ≤2,000m |
| Conductor / busbar capacity | Up to 25mm², manufacturer table |
| Terminal tightening torque | 2N·m |
| Terminal connection | Cable, U-type busbar or pin-type busbar |
| Mounting / feed direction | 35mm EN60715 DIN rail / top or bottom feed |
| Dimensions | Use the original pole-specific mounting drawing below |
Selection and installation
Use the three-pole C63, 400V AC, 50Hz nameplate as the identity of this item. The shared 2025 catalogue lists other currents, poles, frequencies and the H 10kA version; those options are not offered on this page. Some factory 1P C16 photographs bear a 10000A marking despite an M model label, so those photographs and ratings have not been used for this verified 3P 6kA item. Do not apply an AC MCB to DC PV strings or assume residual-current protection. Select a device whose rated short-circuit capacity covers the prospective fault current, with conductor sizing and upstream coordination appropriate to the installation.
Typical applications
Three-phase residential, commercial and light-industrial distribution circuits requiring coordinated overload and short-circuit protection. Motor-starting duty requires a separate starting-current and protection assessment.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.