CHINT · Servo automatic AC voltage regulator
Product overview
The CHINT TND1 uses a servomotor-driven brush and regulator winding to stabilize the AC supply. Select the complete capacity and cooling-construction model, then size the regulator for the measured input voltage and the actual load starting duty.
Technical selection summary
| Manufacturer series | TND1 |
|---|---|
| Phase / connection | Single-phase |
| Standard input range | AC 160–250 V |
| Rated output | AC 220 V ±4% |
| Frequency | 50/60 Hz |
| Catalogue capacity scope | 0.5 / 1 / 1.5 / 2 / 3 / 5 / 10 / 15 / 20 / 30 kVA |
| Cooling and construction | AN natural convection is omitted from the designation; AF identifies forced-air cooling. Use the exact model/outline row |
| Protection thresholds | Output overvoltage 246±4 V and undervoltage 180±8 V; for TNS1 these are phase-voltage values |
| Regulation response | Up to 6 s when input changes within 20 V under the manufacturer reference conditions |
| Environment | -5°C to +40°C; relative humidity ≤90% at +20°C; altitude ≤2000 m; indoor ventilated installation |
Rated output capacity decreases below 198 V input phase voltage (342 V line-to-line for the three-phase series). Allow motor/compressor inrush and phase balance; TNS1 loading per phase must not exceed one third of the total rating. AF and horizontal/vertical versions have different dimensions. The standard input range above does not establish the special 130–230 V supply version; request its exact documentation separately.
Typical applications
- Equipment supplied from fluctuating AC mains within the regulated range
- Industrial, commercial or household loads with appropriate starting and derating margins
Product reference images and drawings
Use the drawing and rating row for the complete manufacturer model and supplied version. Family references may show other constructions.