CHINT · Single-phase AC voltage stabilizer
Product overview
The CHINT TND6 automatically regulates a fluctuating single-phase AC supply. This page covers the manufacturer’s TND6-10/AF and TND6-15/AF ratings, corresponding to the existing 10 kVA and 15 kVA selections. AF denotes fan-assisted cooling; confirm the complete nameplate designation when ordering.
Technical selection summary
| Manufacturer / models | CHINT TND6-10/AF and TND6-15/AF; cooling code may be omitted in the manufacturer designation |
|---|---|
| Phase / frequency | Single-phase AC; 50 Hz in the 2026 sample; confirm the frequency on the ordered nameplate |
| 10 kVA version | TND6-10/AF: 10 kVA, rated output current 45.5 A |
| 15 kVA version | TND6-15/AF: 15 kVA, rated output current 68.2 A |
| Input range for these AF versions | 130–250 V AC |
| Regulated output | 220 V AC with ±4% regulation accuracy |
| Low-input derating | Below 198 V input, reduce the permissible output load according to the matching capacity curve; full kVA is not available over the whole input range |
| Cooling / display | AF fan-assisted cooling; digital operating-parameter display |
| Protection reference | Overtemperature protection disconnects the input; overvoltage protection disconnects the output, according to the 2026 sample |
| Environment / altitude | Indoor, ventilated installation; −5 to +40 °C ambient; 2026 altitude reference ≤1000 m |
| Load-selection margin | Catalogue guide: resistive loads 1.1–1.3 times total load power; inductive/capacitive loads 2.5–3 times, with starting surge and low-input derating considered |
| Output connection restriction | Do not parallel stabilizer outputs; use the exact manufacturer installation instructions |
| Standards reference | Q/ZT 78 |
The retained older table separates smaller 110–250 V models from the 10/15 kVA AF units: only the 130–250 V AF ratings correspond to this page’s selections. Its 50/60 Hz and 2000 m references differ from the current 50 Hz / 1000 m sample; do not combine editions. Confirm the actual nameplate and installation rating. Capacity must also cover motor starting current and the reduced output available at low input voltage.
Typical applications
- Single-phase equipment requiring a regulated 220 V AC supply
- Motor and mixed-load installations selected with adequate starting and derating margin
CHINT TND6 official product documents