CHINT · OUVR-2 Self-Recovery Overvoltage and Undervoltage Protector
Product overview
CHINT OUVR-2 disconnects a single-phase AC 230 V supply during overvoltage or undervoltage and reconnects after voltage recovers and the specified delay expires.
Technical selection summary
| Page scope | 1P+N; AC 230 V; 50 Hz |
|---|---|
| Current options | 32, 40, 50, 63 or 80 A |
| Cutoff values | Overvoltage: 275 V; undervoltage: 161 V |
| Recovery range | 196–253 V |
| Reconnection delay | 30 ± 10 seconds |
The neutral conductor must be connected correctly. This page covers the single-phase 230 V application and does not generate three-phase configurations from the family designation.
Typical applications
- CHINT OUVR-2 disconnects a single-phase AC 230 V supply during overvoltage or undervoltage and reconnects after voltage recovers and the specified delay expires.
Product reference images and drawings