CHINT · Conductive-liquid level relay
Product overview
The CHINT NJYW1 relay controls water supply or drainage using conductive-liquid electrodes. Select the N or B function, maximum electrode lead length and the exact AC control supply for the tank and pump-control circuit.
Technical selection summary
| Manufacturer models | NJYW1-NL1 / NL2 / BL1 / BL2 |
|---|---|
| Function / electrode lead | N: supply or drainage; B: supply/drainage with pump dry-run protection. L1: maximum 1 km; L2: maximum 2 km electrode lead |
| N-series supply | AC 36 V, AC 110/220 V or AC 220/380 V, 50/60 Hz; use the matched terminal arrangement |
| B-series supply | AC 36 / 110 / 220 / 380 V, 50/60 Hz by the exact order row |
| Output contact | N: one changeover; B: separately described 1NO and 1NC arrangement. AC-15 240 V / 0.75 A or 415 V / 0.47 A; Ith 5 A |
| Electrode / power | 24 V electrode control reference; relay consumption below 3 VA |
| Response reference | Operation up to 80 ms; release up to 160 ms |
| Installation / standard | DIN rail or device mounting; -5°C to +40°C; IEC/EN 60947-5-1 |
The 24 V electrode reference is not a DC 24 V power-supply option. This conductive-liquid method is unsuitable for oil, purified water, flammable/explosive chemical liquids or high-density sewage, as stated by the manufacturer. Use a correctly rated contactor for pump power switching and follow the exact N/B terminal diagram.
Typical applications
- Water tank and tower level control
- Water supply/drainage and pump-control circuits suited to conductive liquids
Product reference images and drawings
Match the exact model, construction and supplied revision. Family reference pages can show other ratings or versions.