CHINT · Manual changeover switch
Product overview
CHINT NH40S manual changeover switches transfer and isolate circuits by manual operation. Match the complete frame, poles, handle and utilisation category.
Technical selection summary
| Operating method | Manual changeover. Do not treat NH40S as an automatically controlled NH40SZ transfer assembly. |
|---|---|
| Load duty versus thermal current | Use the voltage-specific AC-21B, AC-22B or AC-23A row for the exact frame. Thermal current is not a universal motor-switching current. |
| 630 A frame example | The referenced NH40S table lists 630 A at 415 V AC-23A and 200 A at 690 V AC-23A for the 630 A thermal-current frame. These values must not be applied to another frame or category. |
| Protection coordination | The manufacturer table includes associated fuse ratings. The manual switch itself is not an automatic overload/short-circuit circuit breaker; coordinate the appropriate protective device. |
Select the exact NH40S frame, poles, handle and voltage-specific utilisation category. The manual switch does not provide an automatic overload or short-circuit trip; coordinate the associated protective device and installation requirements.
Typical applications
- Control or distribution assemblies matched to the exact model and operating duty.
- Replacement procurement with complete manufacturer-code verification.