ABB | MANUAL MOTOR STARTER
Product overview
The ABB MS116-16 manual motor starter combines manual switching, thermal overload and electromagnetic short-circuit protection for the adjustable current range 10-16A. The exact ABB ordering reference is 1SAM250000R1011. It has trip class 10A.
Key features
- Adjustable thermal overload setting and magnetic short-circuit protection
- Trip-free mechanism, phase-loss sensitivity and manual isolation
- Compatible front/side contacts, voltage releases and installation kits
Technical selection summary
| Complete model | MS116-16 |
|---|---|
| ABB order code | 1SAM250000R1011 |
| Adjustable current setting range | 10-16A |
| Number of poles | 3 |
| Trip class | 10A |
| Phase-loss sensitivity | Yes |
| Terminals | Screw terminals |
| Ics, 400V AC | 16kA; open device, per ABB motor protection catalogue |
| Icu, 400V AC | 16kA; open device, per ABB motor protection catalogue |
| Typical motor power, 400V AC-3/AC-3e | 7.5kW; select by actual motor current |
| Rated operational voltage | 690V AC |
| Switching and disconnect function | Manual rotary operation; trip-free mechanism |
| Mounting | 35mm DIN rail |
| Dimensions (W x H x D) | 45 x 90 x 80.1mm |
| Degree of protection | Housing IP20; main terminals IP10 |
| Temperature compensation | -25 to +55°C |
| Applicable standards | IEC/EN 60947-2 and IEC/EN 60947-4-1 |
Set overload protection to the actual motor nameplate current. The stated Ics and Icu are distinct 400V AC open-device ratings from the referenced ABB catalogue; other voltages and enclosed installations have separate ratings. Front contact choices are one module; the right-side slot allows up to two auxiliary modules or one signalling module. Shunt and undervoltage releases are alternatives on the left side. Release AC voltage and frequency must match.
Accessories and installation
Choose the front contact arrangement and terminal type, or a right-side auxiliary/alarm module with its contact arrangement and quantity. AC releases are selected by both frequency and voltage. IB132-G/Y and DMS132-G/Y are separate installation items; the base device is not included in these accessory codes.
The IB132 enclosure permits one side module, one UA1/AA1 release and one front HKF1 module. Selecting an enclosure restricts the side quantity to one. Enclosed operating current and conditional short-circuit ratings must follow ABB instruction 2CDC131028M6805 Rev E; these do not replace open-device Ics/Icu values.
MS116-16 in IB132, 400V AC
| 4.0mm² copper conductor | Motor current ≤15.5A; conditional Iq 10kA |
|---|
ABB IB132 complete installation instructions, Rev E (2026)
| Front Auxiliary Contacts | 1NO+1NC, 1NO, 1NC, 2NO |
|---|---|
| Right-side Accessory | Auxiliary, Trip alarm |
| Remote Release | Shunt opening, Undervoltage |
| Installation | IP65 enclosure, IP65 door mounting |
Typical applications
- Manual motor starting and branch motor protection
- Industrial pump, fan, conveyor and machinery control panels
ABB Motor Protection and Control complete catalogue PDF