Original ABB Tmax T7 1000A molded-case circuit breakers with PR232/P LSI electronic protection. Select the exact breaking class and pole configuration.
Technical selection summary
| Parameter | Specification |
|---|---|
| Original product | Original ABB, as confirmed for these ABB-original listings |
| Rated current / protection | 1000A / PR232/P LSI |
| Breaking classes at AC415V | S: Icu50kA; H:70kA; L:120kA; Ics100% at AC415V. This page offers only the classes in the selectors. |
| Main circuit | IEC AC50/60Hz; operational voltage up to690V;415V breaking values must not be transferred to690V |
| Construction | Manual fixed T7 with front terminals; motor-operated T7M and UL versions have different references |
| Outline reference W x H x D | 3P210 x268 x154mm;4P280 x268 x154mm |
| Protection function | PR231/P: LS/I; PR232/P: LSI; PR332/P LI: long-time and instantaneous functions, according to selected listing |
Series reference photographs may show another current or trip unit. The selected IEC order code and table below define this listing; the1200A UL carton photograph is not a1000/1250/1600A IEC reference.
| Version | Current | Protection | ABB order code |
|---|---|---|---|
| T7S 3P | 1000A | PR232/P LSI | 1SDA062739R1 |
| T7S 4P | 1000A | PR232/P LSI | 1SDA062747R1 |