NewTrend · RD9L-R + YL9M
Product overview
NewTrend RD9L-R automatic operating module paired with a YL9M RCCB. Select the poles, current, residual sensitivity/type and separate module supply.
Technical selection summary
| Parameter | Specification |
|---|---|
| Protection | YL9M instantaneous electromagnetic RCCB without integral overcurrent protection |
| Main circuit | 2P:AC240V; 4P:AC415V; 25/40/63A, 50/60Hz |
| Residual settings | TypeAC or A, 30/100/300mA per supplied NewTrendYL9catalogue |
| Module supply | Separate AC220V or DC12V module versions; not the main-circuit voltage |
| Reclosing | RD9L-R three attempts at10s, 60s, 300s; counter resets after 15minutes without retrip |
| Locking | Manual/automatic selector and mechanical/electronic locking; ensure circuit and load are safe before reclosing |
| Conditional short-circuit | Documented6kAassembly; RCCB Inc/IΔc requires coordinated upstream short-circuit protection |
| Dimensions | Module82x18x78mm; assembly width 53mm2P or88mm4P reference |
| Mounting / environment | DINrail35mm, IP20;-20to+55°C module reference |
The original Type B title, C curve and LSIG fields are unsupported by the suppliedYL9RCCBdocuments and are corrected. This published ordinary automatic-reclosing assembly does not inherit RS485/Wi-Fi functions or a10kAvariant. Automatic reclosing is not fault clearance; upstream overcurrent coordination remains necessary.
Typical applications
- Electrical distribution and motor control
Open technical reference image