NewTrend / OEM · Miniature DC-coil contactor
Product overview
The LP1K listing concerns miniature contactors with DC control coils. Select the full current-frame, auxiliary-contact, coil and terminal code; LC1K AC-coil data in the family comparison describes a different control version.
Technical selection summary
| Listing series | LP1K |
|---|---|
| Frame reference | 6, 9, 12 or 16 A; confirm voltage and utilization category |
| Control circuit | DC coil; complete voltage suffix required |
| Contact selection | Confirm main poles and NO/NC auxiliary arrangement |
| Mounting | DIN rail, plate or PCB solder-pin version; match exact outline |
Coil supply and main-contact load duty are separate selections. Match the exact model column, control voltage, contact diagram and connection style. Confirm OEM identity, approvals, life data and accessory compatibility for the supplied version.
Model-specific reference data
The comparison includes LC1K AC-coil and LP1K DC-coil constructions. Use the matching model, voltage, duty and mounting column.
| Model Number | LC1K06 | LC1K09 | LC1K12 | LC1K16 | LP1K06 | LP1K09 | LP1K12 | LP1K16 |
| Rated operational current (AC-3, 380V) | 6A | 9A | 12A | 16A | 6A | 9A | 12A | 16A |
| Rated operational current (AC-3, 660V) | 5A | 7.5A | 10A | 12A | 5A | 7.5A | 10A | 12A |
| Coil voltage (Control circuit voltage) | AC 230V 240V 380V 415V | DC 220V 230V 240V 250V | ||||||
| Rated operational voltage | 380V, 660V | |||||||
| Rated insulation voltage | 690V | |||||||
| Main and auxiliary contacts | 3P+NO, 3P+NC, 2NO+2NC | |||||||
| Motor power (AC-3, 220/240V) | 1.5KW | 2.2KW | 3KW | 3KW | 1.5KW | 2.2KW | 3KW | 3KW |
| Motor power (AC-3, 380/415V) | 2.2KW | 4KW | 5.5KW | 7.5KW | 2.2KW | 4KW | 5.5KW | 7.5KW |
| Motor power (AC-3, 440V) | 3KW | 4KW | 5.5KW | 7.5KW | 3KW | 4KW | 5.5KW | 7.5KW |
| Motor power (AC-3, 500/660/690V) | 3KW | 4KW | 4KW | 4KW | 3KW | 4KW | 4KW | 4KW |
| Mouting type | DIN Rail / PCB Solder Pin / Plate | |||||||
| Coil Pull-In Voltage | 0.85-1.1 Us | |||||||
| Coil Drop-Out Voltage | 0.2-0.75 Us | ≤0.2 Us | ||||||
| Coil power | Pull-In 40VA, Maintain 4VA | |||||||
| Coil power consumption | 1.2W | |||||||
| Coil Pull-In time | 6-18 ms | |||||||
| Coil Drop-Out time | 5-12 ms | |||||||
| Electrical life | 500 thousand times | |||||||
| Mechanical life | 100 thousand times | |||||||
| Ambient air temperature | -5…40 °C | |||||||
| Operating altitude | 2000 m without derating in temperature | |||||||
| LC1K (AC voltage coil) | |||||||||||||||||
| Volts (50/60Hz) | 12 | 20 | 24 | 36 | 42 | 48 | 110 | 115 | 120 | 127 | 200/ 208 | 220/ 230 | 230 | 230/ 240 | 256 | 277 | 380/ 400 |
| Code | J7 | Z7 | B7 | C7 | D7 | E7 | F7 | FE7 | G7 | FC7 | L7 | M7 | P7 | U7 | W7 | UE7 | Q7 |
| Volts (50/60Hz) | 400 | 400/ 415 | 440 | 480 | 500 | 575 | 600 | 660/ 690 | |||||||||
| Code | V7 | N7 | R7 | T7 | S7 | SC7 | X7 | Y7 | |||||||||
| LP1K (DC voltage coil) | |||||||||||||||||
| Volts | 12 | 20 | 24 | 36 | 48 | 60 | 72 | 100 | 110 | 125 | 155 | 174 | 200 | 220 | 230 | 240 | 250 |
| Code | JD | ZD | BD | CD | ED | ND | SD | KD | FD | GD | PD | QD | LD | MD | MPD | MUD | UD |
| LP1K09105BD: | |
| LP1K means DC coil contactor, LC1K means AC coil contactor | |
| 09 means AC-3 9A rated current | |
| 10 means NO auxiliary contact, 01 means NC auxiliary contact | |
| 5 means PCB Solder Pin type, without 5 means regular DIN Rail type | |
| BD means the coil voltage code |