NewTrend · three-phase monitoring relay
Product overview
The microprocessor-based OMPD-8S monitors a three-phase supply for phase loss, incorrect phase sequence, voltage imbalance, overvoltage and undervoltage. Its LCD and keypad allow adjustment of thresholds and delays. Relay contacts can operate a separate contactor to disconnect the load when a fault occurs.
Technical selection summary
| Model | OMPD-8S |
|---|---|
| Product type | Three-phase voltage and phase monitoring relay |
| Rated supply voltage | 380V AC |
| Operating voltage range | 300–490V AC |
| Frequency | 50/60Hz |
| Protective functions | Overvoltage, undervoltage, phase loss, phase sequence and phase unbalance |
| Output contacts | 1 NO + 1 NC |
| Contact capacity, resistive load | 6A at 250V AC / 30V DC |
| Voltage / asymmetry hysteresis | 10V / 2% |
| Automatic reset time | 1.5s |
| Phase loss / sequence response | 1s / instantaneous |
| Fault memory | Last three faults |
| Protection degree | IP20 |
| Mounting | 35mm DIN rail |
| Measurement error | ≤1% within the adjustable voltage range |
| Mechanical life reference | 100,000 cycles |
| Dielectric strength | >2kV AC for 1 minute |
| Height / depth in side drawing | 80mm / 54mm |
| Housing | Flame-retardant PC |
Electrical characteristics
Settings and indication
The minus and plus keys decrease or increase the selected setting and shift the displayed line voltage. R/S enters parameter settings and provides manual reset. The red front button is marked N/A. OV, UV, UB, SEQ, FAILS and SET identify overvoltage, undervoltage, unbalance, phase sequence, phase loss and setting mode.
Overvoltage, undervoltage and phase-unbalance thresholds and their delays are adjustable. Phase-sequence monitoring may be enabled or disabled. Automatic or manual reset can be selected, and the last three faults can be recalled on the display.
Adjustable protection settings
| Overvoltage threshold | 390–490V or OFF; default 437V |
|---|---|
| Overvoltage delay | 0.1–25s; default 5s |
| Undervoltage threshold | 300–370V or OFF; default 323V |
| Undervoltage delay | 0.1–25s; default 5s |
| Phase-unbalance threshold | 5–29% or OFF; default 10% |
| Phase-unbalance delay | 1–25s; default 5s |
| Phase-sequence protection | ON / OFF; default ON |
| Reset method | AU automatic / HA manual; default AU |
| Fault recall | Records 1, 2 and 3 |
| Exit | End |
Wiring and output
Connect the three monitored phases to the marked inputs. The relay provides one normally open and one normally closed contact for a control circuit; the diagram shows a separate contactor switching the load. Use appropriate protection and isolate the supply before installation or service.
Mounting and applications
Mount on a 35mm DIN rail. Suitable applications include motors, pumps, fans, blowers, compressors, refrigeration units, lifts, elevators, cranes, mining excavators and conveyors.
DIN-rail mounting dimensions
The side drawing shows an 80mm overall height, 54mm depth and the 35mm DIN-rail mounting interface. Allow space for wiring and access to the front controls.