NewTrend · twilight light-control relay
Product overview
NewTrend RB8-01 switches lighting according to ambient light measured by a matching external sensor. The illumination threshold is adjustable from 1 to 100lx, with ON, AUTO and OFF positions. A fixed two-minute switching delay reduces response to brief light changes. The 18mm DIN-rail relay uses AC 110-240V and provides a 16A AC-1 switched-line output.
Technical selection summary
| Model | RB8-01 |
|---|---|
| Function | External-sensor twilight light control |
| Control supply | AC 110-240V |
| Supply frequency | 50/60Hz |
| Supply terminals | L-N |
| Power input | Maximum 2VA |
| Supply tolerance | -15% to +10% |
| Illumination range | 1-100lx |
| Function selector | ON / AUTO / OFF |
| Switching delay | Fixed 2 minutes |
| Sensor tolerance | ±35% |
| Matching sensor codes | LS-01R-0.2m / LS-02R-0.2m |
| Sensor terminals | IN-IN |
| Sensor lead in drawing | 200mm |
| Maximum sensor-cable length | 50m with standard wire, according to current catalogue |
| Sensor panel holes | LS-01: 9.6mm; LS-02: 12mm |
| Output contacts | 1 SPST; 1 normally open switched-line contact |
| Switched-line output terminals | L-4 |
| Contact rating | 16A, AC-1 |
| Contact switching voltage (factory table) | 250VAC / 24VDC |
| Minimum DC breaking power (contact table) | 500mW |
| Supply indication | Green Un LED |
| Output indication | Red R LED |
| Mechanical life | 10,000,000 operations |
| Electrical life (AC-1) | 100,000 operations |
| Operating temperature | -20 to +55°C |
| Storage temperature | -35 to +75°C |
| Mounting | DIN rail to EN/IEC 60715; 18mm module |
| Protection | IP40 front panel / IP20 terminals |
| Operating position | Any |
| Overvoltage category / pollution degree | III / 2 |
| Maximum conductor size | Solid: 1 x 2.5mm² or 2 x 1.5mm²; with sleeve: 1 x 2.5mm² |
| Body dimensions | 90 x 18 x 64mm |
| Overall height in drawing | 95mm including rail-clip projection |
| Weight (current catalogue) | 62g |
| Referenced standard | EN 60255-1 |
Operation
- Connect the matching sensor to the IN terminals and the AC supply to L-N, following the original wiring diagram.
- Select AUTO for light-dependent switching and set the 1-100lx threshold. ON and OFF provide the corresponding manual output states.
- The original function diagram shows a fixed two-minute switching delay. The green Un LED indicates supply and the red R LED indicates output state.
- The LS-01 sensor style uses a 9.6mm panel hole; the LS-02 style uses a 12mm panel hole. Both original sensor drawings show a 200mm lead.
Typical applications
- Street and garden-lighting control using a protected control panel
- Advertisement and shop-window illumination control
- Automatic lighting according to local ambient light
View or download RB8-01 twilight-switch catalogue (PDF)
Product reference images and drawings
Original illumination settings, matching sensors and technical parameters
Original sensor dimensions, two-minute timing, wiring and relay dimensions
Use the matching R-type sensor listed for RB8-01. The relay supply is L-N and the switched-line output is L-4; follow the original wiring diagram rather than treating the output as an isolated dry contact. Use the N-3 control connection only as shown in the exact-model function and wiring diagrams. Confirm the required sensor style and supplied accessories with the order. Installation and wiring must be performed by qualified electricians.