NewTrend · twilight light-control relay
Product overview
NewTrend RB8-02 switches lighting according to ambient light measured by a matching external sensor. The Func control selects x1 or x10 automatic ranges, covering 1-1000lx or 10-10000lx, plus forced ON and OFF positions. A fixed two-minute switching delay reduces response to brief light changes. The 18mm DIN-rail relay uses AC 110-240V and provides a 16A AC-1 switched-line output.
Technical selection summary
| Model | RB8-02 |
|---|---|
| Function | External-sensor twilight light control |
| Control supply | AC 110-240V |
| Supply frequency | 50/60Hz |
| Supply terminals | L-N |
| Power input | Maximum 2VA |
| Supply tolerance | -15% to +10% |
| Illumination range | x1: 1-1000lx; x10: 10-10000lx |
| Function selector | ON / x1 / x10 / OFF |
| Switching delay | Fixed 2 minutes |
| Sensor tolerance | ±35% |
| Matching sensor codes | LS-01D-0.2m / LS-02D-0.2m |
| Sensor terminals | IN-IN |
| Sensor lead in drawing | 200mm |
| Sensor panel holes | LS-01: 9.6mm; LS-02: 12mm |
| Output contacts | 1 SPST; 1 normally open switched-line contact |
| Switched-line output terminals | L-4 |
| Contact rating | 16A, AC-1 |
| Contact switching voltage (factory table) | 250VAC / 24VDC |
| Minimum DC breaking power (contact table) | 500mW |
| Supply indication | Green Un LED |
| Output indication | Red R LED |
| Mechanical life | 10,000,000 operations |
| Electrical life (AC-1) | 100,000 operations |
| Operating temperature | -20 to +55°C |
| Storage temperature | -35 to +75°C |
| Mounting | DIN rail to EN/IEC 60715; 18mm module |
| Protection | IP40 front panel / IP20 terminals |
| Operating position | Any |
| Overvoltage category / pollution degree | III / 2 |
| Maximum conductor size | Solid: 1 x 2.5mm² or 2 x 1.5mm²; with sleeve: 1 x 2.5mm² |
| Body dimensions | 90 x 18 x 64mm |
| Overall height in drawing | 95mm including rail-clip projection |
| Weight (current catalogue) | 65g |
| Referenced standard | EN 60255-1 |
Operation
- Connect the matching sensor to the IN terminals and the AC supply to L-N, following the original wiring diagram.
- Select x1 for 1-1000lx or x10 for 10-10000lx and set the Lx dial. ON and OFF provide the corresponding manual output states.
- The original function diagram shows a fixed two-minute switching delay. The green Un LED indicates supply and the red R LED indicates output state.
- The LS-01 sensor style uses a 9.6mm panel hole; the LS-02 style uses a 12mm panel hole. Both original sensor drawings show a 200mm lead.
Typical applications
- Street and garden-lighting control using a protected control panel
- Advertisement and shop-window illumination control
- Automatic lighting according to local ambient light
View or download RB8-02 twilight-switch catalogue (PDF)
Product reference images and drawings
Original illumination settings, matching sensors and technical parameters
Original sensor dimensions, two-minute timing, wiring and relay dimensions
Use the matching D-type sensor listed for RB8-02. The relay supply is L-N and the switched-line output is L-4; follow the original wiring diagram rather than treating the output as an isolated dry contact. Confirm the required sensor style and supplied accessories with the order. Installation and wiring must be performed by qualified electricians.