People Electric · Low-Voltage Switchgear Assembly
Product overview
People Electric MNS2.0 is a modular low-voltage switchgear system for power distribution and motor control. Its 25mm design module supports project-specific cabinet layouts, functional units and internal separation. Catalogue ratings describe design limits; the complete delivered assembly must be specified and verified for the installation.
Technical selection summary
| Manufacturer / system | People Electric MNS2.0 |
|---|---|
| Rated working voltage | AC400V, 3-phase |
| Rated insulation voltage | AC690V, 3-phase |
| Rated impulse withstand voltage | 8kV |
| Overvoltage / pollution category | III / 3 |
| Rated frequency | Up to 60Hz, as tabulated; confirm the project supply |
| Main bus current, source table | Up to 5500A, with 6300A shown parenthetically. The parenthetical version is not independently selectable without exact design confirmation. |
| Main bus fault withstand, source maxima | Peak up to 220kA; short-time up to 100kA. The table does not state a duration; confirm the required time and verified assembly. |
| Distribution bus current, source table | Up to 1200A, with 2000A parenthetically; exact construction requires confirmation. |
| Distribution bus fault withstand, source table | Peak up to 110kA (176kA parenthetically); short-time up to 50kA (80kA parenthetically). Confirm duration and exact design. |
| Recommended cabinet height | 2200mm |
| Recommended width / depth | Width 400 / 600 / 800 / 1000 / 1200mm; depth 800 / 1000 / 1200mm |
| Design module | E=25mm |
| Separation / ingress protection | Up to Form4; IP30–IP54 depending on exact enclosure and ventilation design |
| Installation conditions | Indoor installation; daily average ambient up to +35°C and maximum +40°C; lower limit −5°C; relative humidity 50% at +40°C, with condensation considered |
| Standard references in original source | GB7251.1-2005 and IEC60439-1; historical source references, not a new independent certification claim |
| Components | Source describes ABB component-based designs. Exact component specifications and complete-assembly conformity must be confirmed for the project. |
Do not combine catalogue maxima or parenthetical values into an unverified assembly rating. Confirm short-time withstand duration, busbar arrangement, protection, separation, ventilation and exact component configuration against the approved project documents. The original manufacturer drawings and complete source PDF are retained.
Typical applications
- Indoor low-voltage distribution switchboards.
- Motor-control centres and engineered building or industrial power systems.
Specify your enquiry
For a focused quotation, include:
- Single-line diagram, load schedule, voltage/frequency and earthing system.
- Required current and fault level including duration, component list, metering and control requirements.
- Cabinet layout, cable entry, IP/separation, ventilation, installation environment and destination.
Download People Electric MNS2 catalogue (PDF)