People Electric · Knife Contact Fuse Link
Product overview
People Electric RT0 fuse links provide general-purpose full-range overload and short-circuit protection in AC distribution circuits. The fuse link uses a powder-filled cartridge and knife contacts with a fusing indicator. Match its current and physical size to the required base and circuit duty.
Technical selection summary
| Manufacturer / series | Original People Electric RT0 |
|---|---|
| Main circuit | AC380V; 50Hz |
| Utilization / breaking capacity | gG full-range general-purpose fuse; 50kA, power factor 0.1–0.2 as tabulated |
| RT0-50 currents | 10, 20, 25, 32, 40, 50A |
| RT0-100 currents | 32, 40, 50, 63, 80, 100A |
| RT0-200 currents | 80, 100, 125, 160, 200A |
| RT0-400 currents | 160, 200, 250, 350, 400A |
| RT0-600 currents | 350, 400, 500, 600A |
| RT0-1000 currents | 700, 800, 900, 1000A |
| Fuse-link dimensions A/B/C/D/E/F/G (mm) | 50 size: 103/66/25/40/4/52/10; 100: 123/68/40/40/6/52/18; 200: 133/68/40/40/6/58/23; 400: 143/68/55/55/6/66/30; 600: 163/68/67/67/6/78.5/36; 1000: 280/90/85/100/6/100/48. Match letters to the original drawing. |
| Components | Fuse link, corresponding base and extraction handle can be separately ordered; confirm the required supply scope |
| Construction | Powder-filled cartridge, copper fuse element, quartz-sand arc-quenching filler and end-cap fusing indicator |
| Installation | Vertical, horizontal or inclined mounting without obvious vibration; installation category III |
| Environment | -5 to +40°C; 24-hour average ≤35°C; altitude ≤2,000m |
The size number is the maximum current of that fuse frame/base; the actual link current must be selected separately. A pictured base or handle is not automatically included. The source ordering example contains an inconsistent set current; use the explicit current table and complete enquiry specification rather than copying that example.
Typical applications
- General-purpose overload and short-circuit protection in AC380V industrial distribution.
- Replacement knife-contact links requiring matching size, current, base and fault-duty rating.
Specify your enquiry
For a focused quotation, include:
- Fuse size and actual link current; AC380V circuit and prospective fault current.
- Fuse link only, base, extraction handle or a clearly specified combination.
- Mounting dimensions, installation conditions, quantity and destination.