People Electric · Moulded Case Circuit Breaker
Product overview
People Electric RDM1 moulded-case circuit breakers are used for distribution switching and fault protection with the specified release and accessories. The series includes different frames, breaking levels and pole/voltage versions. Select the exact documented combination before choosing current; a common frame number does not establish a common breaking rating or pole arrangement.
Technical selection summary
| Manufacturer / series | Original People Electric RDM1 |
|---|---|
| Main circuit | AC50/60Hz; AC400V, or AC690V only for the exact variants with a tabulated 690V rating |
| 63A frame currents | 10, 16, 20, 25, 32, 40, 50, 63A |
| 125A frame currents | 16, 20, 25, 32, 40, 50, 63, 80, 100, 125A |
| 250A frame currents | 100, 125, 160, 180, 200, 225, 250A |
| 400A frame currents | 225, 250, 315, 350, 400A |
| 630A frame currents | 400, 500, 630A |
| 800A frame currents | 630, 700, 800A |
| 1250A frame currents | 700, 800, 1000, 1250A |
| Insulation voltage | RDM1-63: 500V; other frames: 800V, as stated in the introduction |
| 4P neutral codes | A: unswitched N without overload release. B: N switches with the other poles, without overload release; B is the source default when the neutral code is omitted. |
| Release types | Instantaneous release (200-series accessory codes) or thermal-magnetic/double release (300-series codes); specify the exact application and accessory code. |
| Internal accessories | Shunt release, undervoltage release, auxiliary/alarm contacts and combinations are documented. Availability and accessory supply must match the exact ordered version. |
| Mounting / environment | Vertical or horizontal; altitude ≤2,000m; -5 to +40°C, daily average ≤35°C; pollution degree 3; maximum inclination 22.5° |
| RDM1-63L: Icu / Ics | AC400V: 25/12.5kA; poles 3P |
| RDM1-63M: Icu / Ics | AC400V: 50/25kA; poles 3P, 4P |
| RDM1-63H: Icu / Ics | AC400V: 50/25kA; poles 3P |
| RDM1-125L: Icu / Ics | AC400V: 35/25kA; poles 2P, 3P, 4P |
| RDM1-125M: Icu / Ics | AC400V: 40/35kA; AC690V: 10/5kA; poles 2P, 3P, 4P |
| RDM1-125H: Icu / Ics | AC400V: 85/50kA; AC690V: 20/10kA; poles 3P, 4P |
| RDM1-250L: Icu / Ics | AC400V: 35/25kA; poles 2P, 3P, 4P |
| RDM1-250M: Icu / Ics | AC400V: 50/35kA; AC690V: 10/5kA; poles 2P, 3P, 4P |
| RDM1-250H: Icu / Ics | AC400V: 85/50kA; AC690V: 10/5kA; poles 3P, 4P |
| RDM1-400C: Icu / Ics | AC400V: 50/35kA; poles 3P |
| RDM1-400L: Icu / Ics | AC400V: 50/35kA; AC690V: 10/5kA; poles 3P, 4P |
| RDM1-400M: Icu / Ics | AC400V: 65/42kA; AC690V: 10/5kA; poles 3P, 4P |
| RDM1-400H: Icu / Ics | AC400V: 100/65kA; AC690V: 10/5kA; poles 3P, 4P |
| RDM1-630L: Icu / Ics | AC400V: 50/25kA; poles 3P, 4P |
| RDM1-630M: Icu / Ics | AC400V: 65/32.5kA; AC690V: 10/5kA; poles 3P, 4P |
| RDM1-630H: Icu / Ics | AC400V: 100/60kA; poles 3P, 4P |
| RDM1-800M: Icu / Ics | AC400V: 75/50kA; AC690V: 20/10kA; poles 3P, 4P |
| RDM1-800H: Icu / Ics | AC400V: 100/65kA; poles 3P, 4P |
| RDM1-1250M: Icu / Ics | AC400V: 65/35kA; AC690V: 20/10kA; poles 3P, 4P |
Only combinations explicitly listed in the main technical tables are offered. Parenthesized special 6A (63A frame) and 10A (125A frame) entries require separate confirmation and are not offered here. AC690V is not available as a universal option. A/B neutral choices apply only to 4P. The source drawing caption RDM1-125M is not used as proof of 1250A-frame dimensions; obtain the exact mounting drawing for that frame. Confirm release, accessory supplies and exact order code before purchase.
Typical applications
- AC industrial and commercial distribution circuits requiring an exact MCCB frame, pole arrangement and fault-level rating.
- Distribution or motor-protection applications using the correctly specified release and coordinated accessories.
Specify your enquiry
For a focused quotation, include:
- Exact frame/level/poles/AC-voltage combination, rated current and prospective fault current.
- Instantaneous or thermal-magnetic release, distribution or motor application, accessory code and exact auxiliary supplies.
- Required handle/mechanism, front/rear/plug-in connection, exact mounting drawing, quantity and destination.
Download People Electric RDM1 catalogue (PDF)