DELIXI ELECTRIC · DELIXI CDC19s Capacitor Contactor, 12–90 kvar at 400V
Product overview
DELIXI CDC19s switches capacitor banks for power-factor correction. Select the linked frame/capacitor-duty and auxiliary-contact version, then choose its control coil.
Technical selection summary
| Product type | 3-pole capacitor-duty contactor; AC-6b application |
|---|---|
| Capacitor duty at 380/400 V | 25: 12; 32: 18; 43: 20; 63: 30; 95: 45; 115: 60; 150: 80; 170: 90 kvar |
| Capacitor duty at 220/230 V | 25: 6; 32: 9; 43: 10; 63: 15; 95: 22.5; 115: 35; 150: 46; 170: 52 kvar |
| Auxiliary contact codes | 11: 1NO+1NC; 20: 2NO; 02: 2NC; 12: 1NO+2NC; 21: 2NO+1NC; 32: 3NO+2NC |
| Permitted frame / auxiliary pairs | 25/32/43: 11, 20 or 02; 63/95/115: 12 or 21; 150/170: 32 only |
| Control coils | F: AC110 V; M: AC220 V; Q: AC380 V; 50 Hz as documented |
| Dual voltage markings | 25–115 M and Q may be marked 220/230 V and 380/400 V; 150/170 use 220 V and 380 V respectively |
Frame numbers are ordering identifiers, not uniform capacitor switching currents. For 63/95/115 frames, use auxiliary codes 12/21 shown in the technical table and manufacturer diagram; the old selection image contains inconsistent 11/20 labels. Capacitor kvar must be evaluated at its actual operating voltage.
DELIXI official English user manual (August 2022)
Typical applications
- DELIXI CDC19s switches capacitor banks for power-factor correction.
Open retained manufacturer catalogue image
Product reference images and drawings