People Electric · Knife Contact Fuse Link
Product overview
People Electric RDT16 knife-contact fuse links provide full-range gG protection for AC distribution circuits. The manufacturer main rating table defines each size/current combination, voltage and breaking capacity. Original product nameplates corroborate the500V/660V ratings of the smaller sizes.
Technical selection summary
| Manufacturer / series | Original People Electric RDT16 |
|---|---|
| Utilisation category | gG; full-range general-purpose fuse link |
| Frequency | AC50Hz |
| Size 00C, fuse-link currents | 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100A |
| Size 00, fuse-link currents | 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160A |
| Size 0, fuse-link currents | 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160A |
| Size 1, fuse-link currents | 80, 100, 125, 160, 200, 250A |
| Size 2, fuse-link currents | 125, 160, 200, 250, 315, 400A |
| Size 3, fuse-link currents | 315, 400, 500, 630A |
| Size 4, fuse-link currents | 800, 1000A |
| Size 4a, fuse-link currents | 1000, 1250A |
| Sizes00C,00,0,1,2,3 voltage / breaking capacity | AC500V:120kA;AC660V:50kA |
| Sizes4 /4a voltage / breaking capacity | AC380V:100kA |
| Base current ratings by size | 00C:100A;00/0:160A;1:250A;2:400A;3:630A;4:1000A;4a:1250A |
| Construction | Ceramic cartridge, quartz-sand arc-quenching filler, knife contacts and indicator/impactor version as ordered |
| Environment | −5 to +40°C;24-hour average≤35°C; altitude≤2,000m |
| Associated components | Matching fuse base and handling accessory ordered separately; confirm exact dimensions and indicator/impactor arrangement |
Current buttons are fuse-link ratings and are restricted by size. Voltage and breaking capacity follow that size;500V/660V ratings do not extend to the380V-only sizes4/4a. This page offers the documented500/660V and380V schedules. Confirm the exact nameplate, fuse base, indicator/impactor and protection coordination before ordering.
Typical applications
- Overload and short-circuit protection in compatible industrial AC distribution circuits.
Specify your enquiry
For a focused quotation, include:
- Fuse size, link current, actual circuit voltage and prospective fault current.
- Fuse link only or matching base/accessories, indicator/impactor requirement and mounting dimensions.
- Quantity and destination.
Download People Electric RDT16 catalogue (PDF)