People Electric · Air Circuit Breaker
Product overview
People Electric RDSW6 intelligent air circuit breakers provide main distribution switching and coordinated fault protection in industrial and building power systems. Select a supported frame/pole arrangement and load current, then match the voltage and fault level to the tabulated breaking ratings. Controller functions and accessories must be specified for the actual protection scheme.
Technical selection summary
| Manufacturer / series | Original People Electric RDSW6 |
|---|---|
| Main circuit | AC400V or AC690V; 50Hz |
| 1000A frame currents | 200, 400, 630, 800, 1000A |
| 2000A frame currents | 630, 800, 1000, 1250, 1600, 2000A |
| 3200A frame currents | 2000, 2500, 2900, 3200A |
| 4000A frame currents | 3200, 3600, 4000A |
| 6300A frame currents | 4000, 5000, 6300A; 6300A rated current is 3P only |
| AC400V Icu / Ics by frame | 1000A: 42/30kA; 2000A: 80/50kA; 3200A: 80/50kA; 4000A: 80/65kA; 6300A: 120/100kA |
| AC690V Icu / Ics by frame | 1000A: 25/20kA; 2000A: 50/40kA; 3200A: 65/50kA; 4000A: 65/65kA; 6300A: 85/75kA |
| 1-second Icw at AC400V / AC690V | 1000A frame: 30/20kA; 2000A: 50/40kA; 3200A: 65/50kA; 4000A: 65/50kA; 6300A: 85/65kA |
| Poles / neutral | 3P or 4P, with the 6300A current limitation above. 4P neutral-current options are 50% In or 100% In; specify the required exact version. |
| Rated insulation / impulse withstand voltage | Ui 1000V; Uimp 12kV |
| Controllers | L: electronic, current indication lights; M: standard, digital current display; H: communication type with current/voltage display |
| Controller and standard accessory supply choices | AC230V, AC400V, DC220V or DC110V; confirm the supply of each accessory independently |
| Installation | Fixed or draw-out; horizontal/vertical connection and exact dimensions must match the frame drawing |
| Undervoltage release | Optional, AC230V or AC400V; instantaneous or delayed versions require explicit selection |
| Opening / closing time | 25–30ms without added delay; closing ≤70ms |
| Environment / utilization | -5 to +40°C; daily average ≤35°C; altitude ≤2,000m; pollution degree 3; category B |
| Standards stated | IEC 60947-2; GB 14048.2 |
The frame/pole selection restricts rated current; 6300A cannot be selected with 4P. Neutral rating, protection settings, busbar connection, accessory supplies and interlocks must be stated in the enquiry. The control-voltage button is not the main-circuit voltage and does not automatically specify every accessory coil. Optional undervoltage and communication accessories are not assumed included.
Typical applications
- Main distribution protection in factories, power stations and high-rise buildings.
- AC690V industrial or mining distribution within the selected voltage, frame and fault-level ratings.
Specify your enquiry
For a focused quotation, include:
- Frame/poles, rated current, AC voltage, prospective fault current and required neutral rating for 4P.
- L/M/H controller, protective functions/settings, auxiliary supply and the supply of each installed release/motor.
- Fixed or draw-out installation, busbar direction, switchboard drawings, interlocks, quantity and destination.
Download People Electric RDSW6 catalogue (PDF)