People Electric · Motor Starting Autotransformer
Product overview
People Electric QZB autotransformers reduce the starting voltage and current of compatible three-phase squirrel-cage induction motors during infrequent starting. The primary and secondary share one winding, so this is not an isolating transformer or a continuous-duty distribution transformer. Confirm the motor power, starting load, tap connections and duty with the quotation.
Technical selection summary
| Manufacturer / offered series | Original People Electric QZB; non-K versions only |
|---|---|
| Published models | QZB-225kW, QZB-260kW, QZB-300kW, QZB-400kW |
| Input supply | Three-phase AC380V;50Hz; connect the input at the100% terminals |
| Designation unit | kW motor-starting size designation; do not treat it as a continuous output kVA rating |
| Operating duty | Infrequent motor starting; each initial starting period≤15s |
| Output / tap requirement | Confirm the required reduced-voltage ratio, terminal scheme and motor-load coordination before ordering; no unspecified tap percentage is offered |
| Winding relationship | Primary and secondary use a common winding; no galvanic isolation |
| 225kW dimensions | B×D×E=565×185×430mm; mountingA=310±5mm,C=140±5mm; slot12×20mm |
| 260kW dimensions | 565×195×430mm; mounting310±5×145±5mm; slot12×20mm |
| 300kW dimensions | 565×200×430mm; mounting310±5×160±5mm; slot12×20mm |
| 400kW dimensions | 565×230×435mm; mounting310±5×160±5mm; slot12×25mm |
| Ambient conditions | −5 to+40°C;24-hour average≤35°C; altitude≤2000m |
| Standards stated | GB14048.4;JB/T8752 |
| Reference edition | Manufacturer Chinese power-supply handbook printed010–011; completePDF retained |
This page is restricted to four non-K QZB models with consistent model units and dimensions. The K-suffix definition and several K-model units differ between source editions, so no K variant is offered here. Original photos are manufacturer series illustrations. Starting time, restart intervals, protection and reduced-voltage taps must be confirmed for the actual motor and load.
Typical applications
- Reduced-voltage infrequent starting of compatible three-phase squirrel-cage induction motors.
Specify your enquiry
For a focused quotation, include:
- QZB model and quantity; motor rated power/current,380V50Hz supply and load type.
- Required voltage-reduction ratio, terminal wiring, start duration and starts per hour.
- Protection coordination, installation envelope, documentation and destination.
Download People Electric QZB catalogue (PDF)