NewTrend · three-phase high-spec static var generator
Product overview
NewTrend Y-SVG-PLUS is a three-phase static var generator for dynamic reactive-power compensation and three-phase load-unbalance correction. The 220VAC version is available at 37 or 50kvar; the 380VAC version at 75 or 100kvar. Both voltage platforms support 3P3W and 3P4W grids, rack or wall mounting, a full response below 10ms and two external current-sampling channels.
Technical selection summary
| Model | Y-SVG-PLUS |
|---|---|
| Rated capacity / voltage | 37 or 50kvar: AC 220V; 75 or 100kvar: AC 380V |
| Voltage tolerance | -20% to +20% |
| Grid configuration | 3P3W / 3P4W |
| Operating frequency | 50/60Hz; operating range 45–63Hz |
| Function | Reactive-power compensation / reactive-power plus three-phase unbalance compensation |
| Reactive compensation rate | ≥99% |
| Residual unbalance after compensation | ≤5%, catalogue value |
| Neutral-line filtering | Up to 3× phase filtering capacity; neutral-connected applications |
| Transient / full response | <50µs / <10ms |
| Overall efficiency | ≥97% |
| Switching frequency | 16kHz |
| Overload capability | 1.2× rated for 60 seconds |
| Current sampling | Two external current-sampling channels |
| Communication | 2× RS485; Wi-Fi supported |
| Mounting / cable entry | Wall-mounted: top entry; rack-mounted: rear entry |
| Protection rating | IP20; IP54 customization described separately in the catalogue |
| Cooling | Forced air cooling |
| Noise | ≤65dB |
| Ambient temperature | -10 to +50°C; derating above 40°C, catalogue states capacity reduction ≤30% |
| Relative humidity | ≤90%; no condensation at monthly minimum 25°C |
| Altitude | <2000m; above 2000m derate per GB/T 3859.2 |
| Pollution degree | ≤Class III |
| Protection functions | Overload, software/hardware overcurrent, grid over-/undervoltage, voltage unbalance, power-supply failure, overtemperature, abnormal frequency, short circuit and resonance protection |
| EMC, catalogue declaration | Radiated and conducted emission (RE/CE) meet Class A test standard |
| Catalogue enclosure dimensions | 500 × 730 × 240mm; confirm exact mounting arrangement |
| Parallel operation | Multiple modules supported |
Operation
- The unit connects in parallel with the load and supplies or absorbs reactive current. Full load current does not pass through the SVG.
- Select reactive-power compensation alone or reactive-power compensation with three-phase unbalance correction. Neutral-line filtering applies to installations with a neutral conductor.
- Two external current-sampling channels support low- or high-voltage-side sampling and reactive-component compensation arrangements.
Typical applications
- Industrial feeders with variable reactive-power demand
- Commercial buildings, data centres and EV charging facilities
- Three-phase feeders requiring reactive-power and load-unbalance compensation
View or download Y-SVG-PLUS original family catalogue, September 2026 (PDF)
Product reference images and drawings
The main and gallery photographs illustrate the shared Y-SVG wall-mounted family enclosure. The original PDF also shows a rack-mounted enclosure. The listed capacities are voltage-specific: 37/50kvar at 220V and 75/100kvar at 380V. Installation and wiring must be performed by qualified electricians.