NewTrend Y-SVG-Cabinet integrates AC distribution, SVG power modules and a monitoring system in a floor-standing cabinet for dynamic reactive-power compensation. The family covers five voltage platforms from 220V to 800V, with voltage-dependent cabinet capacity ranges from 50 to 900kvar. Each cabinet is configured to the required capacity within its voltage-platform range.
Technical selection summary
| Model | Y-SVG-Cabinet |
|---|---|
| Cabinet composition | AC distribution, SVG power modules and monitoring system |
| AC 220V capacity range | 50–300kvar |
| AC 380V capacity range | 100–600kvar |
| AC 500V capacity range | 90–540kvar |
| AC 690V capacity range | 100–720kvar |
| AC 800V capacity range | 150–900kvar |
| Exact cabinet capacity | Project-specific within the published voltage-platform range; discrete steps not specified in the catalogue |
| Operating voltage tolerance | 220/380/500V: -20% to +20%; 690V: -20% to +15%; 800V: -20%, 850V maximum |
| Grid configuration | 220–690V: 3P3W / 3P4W; 800V: 3P3W only |
| Function | 220–690V: reactive / reactive plus unbalance compensation; 800V: reactive only |
| Reactive compensation rate | ≥99%, September 2026 catalogue |
| Residual unbalance | ≤5% on supported configurations |
| Transient / full response | <50µs / <10ms |
| Operating frequency | 50/60Hz; 45–63Hz range |
| Overall efficiency | ≥97% |
| Switching frequency | 220/380V: 16kHz; 500/690/800V: 12.8kHz |
| Current sampling | Two external current-sampling channels |
| Communication | 2× RS485; Wi-Fi supported |
| Overload capability | 1.2× rated for 60 seconds |
| Mounting / cable entry | Vertical floor-standing; top and bottom cable entry |
| Protection rating | IP20; IP54 customization described separately in catalogue |
| Cooling / noise | Forced-air cooling; ≤75dB |
| Ambient temperature | -10 to +50°C; above 40°C derating, catalogue capacity reduction ≤30% |
| Relative humidity | ≤90%, no condensation at monthly minimum 25°C |
| Altitude | <2000m; above 2000m derate per GB/T 3859.2 |
| Pollution degree | ≤Class III |
| Protection functions | Overload, software/hardware overcurrent, grid over-/undervoltage, voltage unbalance, power-supply failure, overtemperature, abnormal frequency and short circuit protection |
| Maximum-capacity cabinet outline | 1250 × 1000 × 2200mm; adjustable according to capacity |
| Cabinet weight, capacity-dependent | 220/380V: maximum 450kg; 500/690/800V: maximum 620kg |
| Parallel operation | Multiple modules supported |
Operation
- The cabinet connects in parallel with the load and combines AC distribution, SVG modules and system monitoring.
- The 220–690V platforms support reactive compensation or reactive plus three-phase unbalance compensation. The 800V platform is 3P3W with reactive compensation only.
- The published capacities are platform ranges, rather than a list of discrete orderable steps. Exact capacity, module arrangement and cabinet outline are confirmed for the installation.
Typical applications
- Industrial and commercial reactive-power compensation systems
- Centralized cabinet installations serving variable reactive loads
- Three-phase load-balancing applications on supported 220–690V platforms
View or download Y-SVG-Cabinet original catalogue, September 2026 (PDF)
Product reference images and drawings
Main and gallery images are two original cabinet-family enclosure examples from the product webpage and catalogue; enclosure arrangement depends on capacity and project configuration. The stated outline is for maximum-capacity cabinets and is not a universal size. Installation and wiring must be performed by qualified electricians.