NewTrend · high-spec advanced static var generator
Product overview
NewTrend Y-ASVG-PLUS combines reactive-power, 2nd–50th harmonic-current and three-phase unbalance compensation. The AC 220V platform is rated at 37 or 50kvar and the AC 380V platform at 75 or 100kvar. Both support 3P3W/3P4W and wall or rack mounting. These kvar values are reactive compensation ratings; a separate harmonic-current rating is not specified for each capacity.
Technical selection summary
| Model | Y-ASVG-PLUS |
|---|---|
| Rated capacity meaning | Catalogue reactive-power compensation rating, kvar |
| Harmonic compensation | 2nd–50th order; current harmonic compensation rate ≥95%, individually adjustable |
| Harmonic-current rating | A separate rated A value is not specified for each kvar capacity |
| Rated capacity / voltage | 37 or 50kvar: AC 220V; 75 or 100kvar: AC 380V |
| Voltage tolerance | -20% to +20% |
| Grid configuration | 3P3W / 3P4W |
| Operating frequency | 50/60Hz; operating range 45–63Hz |
| Function | Reactive / harmonic / three-phase unbalance compensation, individually or combined |
| Reactive compensation rate | ≥99% |
| Residual unbalance after compensation | ≤5%, catalogue value |
| Neutral-line filtering | Up to 3× phase filtering capacity; neutral-connected applications |
| Transient / full response | Reactive response <10ms; harmonic response <40ms |
| Overall efficiency | ≥97% |
| Switching frequency | 16kHz |
| Overload capability | 1.2× rated for 60 seconds |
| Communication | 2× RS485; Wi-Fi supported |
| Mounting / cable entry | Wall-mounted: top entry; rack-mounted: rear entry |
| Protection rating | IP20; IP54 customization described separately in the catalogue |
| Cooling | Forced air cooling |
| Noise | ≤65dB |
| Ambient temperature | -10 to +50°C; derating above 40°C, catalogue states capacity reduction ≤30% |
| Relative humidity | ≤90%; no condensation at monthly minimum 25°C |
| Altitude | <2000m; above 2000m derate per GB/T 3859.2 |
| Pollution degree | ≤Class III |
| Protection functions | Overload, software/hardware overcurrent, grid over-/undervoltage, voltage unbalance, power-supply failure, overtemperature, abnormal frequency, short circuit and resonance protection |
| EMC, catalogue declaration | Radiated and conducted emission (RE/CE) meet Class A test standard |
| Catalogue enclosure dimensions | 500 × 730 × 240mm, catalogue sequence W × D × H; confirm exact mounting arrangement |
| Parallel operation | Multiple modules supported |
Operation
- The ASVG connects in parallel with the load and injects controlled compensation current for reactive power, current harmonics and three-phase unbalance.
- Select individual or combined compensation functions. Individual harmonic compensation covers the 2nd through 50th orders.
- Neutral-line zero-sequence filtering capacity is stated as three times the phase filtering capacity for neutral-connected installations. Confirm combined-duty and harmonic-current requirements for the chosen reactive rating.
Typical applications
- Industrial and commercial distribution with reactive and nonlinear loads
- Data centres, UPS feeders and variable-speed-drive installations
- Three-phase installations requiring reactive, harmonic and load-unbalance compensation
View or download Y-ASVG-PLUS original catalogue, September 2026 (PDF)
Product reference images and drawings
Photographs show original ASVG-PLUS wall-mounted and rack-mounted enclosure examples. The 37/50kvar capacities apply to220V and75/100kvar to380V. Dimensions retain the catalogue W×D×H sequence; confirm exact physical arrangement for the selected mounting. Installation and wiring must be performed by qualified electricians.