NewTrend · ELR-3C
Product overview
NewTrend ELR-3C external-CT earth-leakage protection relay. Select the actual supply construction and intended adjustable residual-current, delay and reset settings.
Technical selection summary
| Parameter | Specification |
|---|---|
| Function | Earth-leakage relay for an external matched zero-sequence CT and separate tripping device |
| Supply constructions | 12VAC/DC;24/48VAC/DC;110VAC/DC plus230/400VAC, three distinct constructions |
| Residual settings | 0.025-0.25A,0.25-2.5A or2.5-25A using multipliers |
| Delay settings | 0.02-0.5s or0.2-5s using x1/x10 |
| Output | One changeover contact,5A250V; residual adjustment is not the output contact rating |
| Controls | Front TEST/RESET; manual/automatic reset; toroidal-circuit interruption monitoring per source |
| Outline | 52.5mm wide x85mm high x73mm deep;35mm DIN rail |
| Protection / supply load | IP20;≤3VA per retained supplier table |
| CT scope | A matching CT is selected separately. The CT photograph is an illustration, not proof of interchangeability of CT ratios |
Owner confirms three separate supply constructions. Repeated terminal numbers in different supply-version diagrams do not make one universal12-400V input. Wire only against the matching supplied unit labels.25-250A requires an external multiplier and is not a standard selectable range.
Typical applications
- Earth-leakage monitoring using a matched external CT
Open technical reference image