CHINT · Air circuit breaker
Product overview
This CHINT NA1 listing covers 1000 A, three-pole M-controller versions in the NA1-1000X or NA1-2000X frame, with fixed or draw-out installation. The requested 220 V is an auxiliary/control-supply requirement.
Technical selection summary
| Manufacturer selection | NA1-1000X-1000M/3P / NA1-2000X-1000M/3P |
|---|---|
| Frame | NA1-1000X or NA1-2000X, each explicitly rated 1000 A on this page |
| Current / pole scope | 1000 A; 3P; M standard controller |
| Main-circuit supply | AC 50/60 Hz; exact AC 400/415/690 V duties depend on frame and voltage column |
| Fault-duty reference | At AC 400 V: NA1-1000X Icu 42 kA / Ics 30 kA; NA1-2000X Icu 80 kA / Ics 65 kA |
| Protection / operation | Use the exact intelligent-controller functions and settings. Undervoltage protection requires the appropriate release/accessories |
| Installation and connections | Fixed or draw-out by complete order; confirm chassis, horizontal/vertical busbars and terminal drawing |
| Manufacturer standard | IEC/EN 60947-2 |
NA1-1000X and NA1-2000X at 1000 A are different frames and fault duties. The auxiliary AC 220/230 V option is separate from the AC main-circuit rating. Confirm motor/manual operation, releases, contacts, wiring and installation before supply.
Typical applications
- Low-voltage main distribution switchgear
- Replacement procurement matched to the exact frame and controller
Product reference images and drawings
Match the exact model, construction and supplied revision. Family reference pages can show other ratings or versions.