DELIXI · RPCF
Product overview
DELIXI RPCF automatic reactive power controller with16 compensation outputs. Select the matched static or dynamic control version and AC supply.
Technical selection summary
| Parameter | Specification |
|---|---|
| Application | Automatic capacitor compensation in balanced three-phase low-voltage systems |
| Steps / sensing | Up to16 outputs;AC0-5A current input;45-65Hz |
| Static J | For AC contactors;relay contact capacity AC220V5A |
| Dynamic D | Active DC12V signal,10mA/channel;match composite or non-contact switching devices |
| Power / protection | 10VA;IP30 enclosure |
| Panel / cutout | 146x146x82mm;139x139mm panel cutout |
| Communication | Z communication is custom,requires its own protocol;not standard on every unit |
| Wiring | Separate220V/380V andJ/D diagrams retained;follow exact selected version |
This balanced common-compensation manual does not establish RPCF3 mixed-compensation ratings. The output signal is separate from the controller power supply;J/D wiring cannot be interchanged.
Typical applications
- Balanced low-voltage capacitor compensation
Download complete original reference PDF