The CNC Electric YCS6-C40 is a pluggable DC surge protective device for photovoltaic DC circuits. This listing covers the 2-pole, DC 1000V version with a nominal discharge current of 20kA and maximum discharge current of 40kA (8/20 microseconds). The original module is marked YCS6-C; YCS6-C40 is the complete type in the manufacturer selection table.
Technical selection summary
| Brand / complete type | CNC Electric / YCS6-C40 |
|---|---|
| Selected configuration | 2P; maximum continuous operating voltage Uc DC 1000V |
| Discharge current (8/20 microseconds) | In 20kA; Imax 40kA |
| Voltage protection level Up | ≤3.6kV at Uc DC 1000V |
| Response time | <25ns |
| Protection / installation | IP20; 35mm DIN rail; pluggable modules |
| Condition indicator | Green: normal; red: failed module |
| Minimum conductor cross-section | L/N 4mm²; earth 6mm² (C40 table) |
| Recommended upstream coordination | 32A fuse or circuit breaker; coordinate with the actual DC circuit |
| Application conditions | Ambient -25°C to +40°C; altitude ≤2000m; pollution degree 3 |
| Reference dimensions | 18mm per pole; 36mm for 2P; depth 67mm; see original drawing |
| Original marking | IEC 61643-1 printed on the manufacturer product photo |
Selection and installation
Select the DC 1000V C40 column when reading the shared family table. AC versions, other discharge-current classes and other voltage ratings are not included in this configuration. The catalogue gives extended component temperature limits separately; these do not replace the application ambient conditions above. Remote signalling is an optional accessory and is not assumed to be included. Use suitable upstream protection and qualified DC installation practices.
Typical applications
Surge protection in photovoltaic DC distribution and DC power circuits within the verified voltage and current limits.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.