CNC Electric · YCS7N
Product overview
The YCS7N modular AC surge protective device is installed at low-voltage distribution incoming circuits. The series includes voltage-limiting discharge-current versions and impulse-current versions. Use the appropriate module configuration for the earthing arrangement and coordinated downstream protection.
Technical selection summary
| Brand | CNC Electric |
|---|---|
| Model | YCS7N |
| Standard listed | IEC61643-11 |
| AC supply frequency | 50/60Hz |
| Voltage-limiting versions | Uc275V / 440V; In/Imax 5/10, 10/20, 20/40, 30/60 or 40/80kA (8/20µs) |
| Up at Uc275V | 0.7 / 1.2 / 1.5 / 1.8 / 2.0kV, corresponding to the five In/Imax ratings above |
| Up at Uc440V | 1.0 / 1.5 / 2.2 / 2.4 / 2.5kV, corresponding to the five In/Imax ratings above |
| Impulse-current versions | Iimp12.5kA or 15kA (10/350µs); Uc275V / 385V; see original table |
| Response time | Voltage-limiting versions <25ns; impulse versions <100ns |
| Temperature | −40 to +80°C |
| Mounting | 35mm DIN rail; 18mm module width |
| Pole widths | 1P 18mm; 2P 36mm; 3P 54mm; 4P 72mm |
| Wiring arrangements | TT, TN-S, TN-C and 3+1 arrangements shown in the original wiring diagrams |
| Remote signalling | Optional R version; original drawing shows NO/C/NC fault contact |
Selection and installation
The selectors on this page cover the voltage-limiting In/Imax versions. Impulse-current and N–PE modules are listed separately in the original catalogue and must not be treated as interchangeable with the 8/20µs ratings. Select the earthing-system wiring, Uc and discharge rating together. Module condition must be inspected and a failed module replaced. Installation and earthing require a qualified electrician.
Typical applications
Building incoming distribution boards; AC power-distribution surge protection; coordinated protection with downstream SPDs.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.