CNC Electric · YCS8-S
Product overview
The YCS8-S is a pluggable photovoltaic DC surge protective device for diverting transient overvoltage to earth. It offers T2 and T1+T2 versions, thermal disconnection and a green/red condition window. Optional remote signalling reports module condition.
Technical selection summary
| Brand | CNC Electric |
|---|---|
| Model | YCS8-S |
| Test category | T2 or T1+T2 |
| Voltage / poles | DC600V: 2P; DC1000V: 3P; DC1500V: 3P |
| Nominal discharge current In | 20kA, 8/20µs |
| Maximum discharge current Imax | 40kA, 8/20µs |
| Impulse current Iimp | 6.25kA, 10/350µs for T1+T2 only |
| Voltage protection level Up | 2.2kV at 600V; 3.6kV at 1000V; 5.6kV at 1500V |
| Response time | ≤25ns |
| Remote signal | Optional changeover contact; maximum conductor 1.5mm² |
| Remote contact ratings | AC250V 0.5A; DC250V 0.1A / DC125V 0.2A / DC75V 0.5A |
| Main connection | Maximum 35mm² conductor; terminal torque 4.5Nm |
| Mounting | 35mm DIN rail |
| Protection / enclosure | IP20; UL94 V-0 material classification |
| Environment | −40 to +70°C; 5–95% RH; −500 to 2000m altitude |
| Standards listed | IEC61643-31:2018; EN50539-11:2013+A1:2014 |
Selection and installation
A green window indicates normal condition and red indicates replacement is required. Select the DC voltage, pole arrangement and surge test category together. T2 versions do not carry the T1+T2 impulse-current value. Follow the selected voltage-version wiring and coordinate upstream protection and earthing. The original technical figures below cover the upgraded YCS8-S version.
Typical applications
Photovoltaic combiner boxes; PV DC distribution cabinets; surge coordination in compatible DC power systems.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.