CNC Electric · YC9VA-3
Product overview
The CNC Electric YC9VA-3 is a digital three-phase voltage and current display protector. This page selects the 63A AC380V line-to-line version with adjustable overvoltage, undervoltage, overcurrent and restart timing.
Technical selection summary
| Manufacturer model | YC9VA-3 |
|---|---|
| Selected rating | 63A; three-phase AC380V L-L |
| Operating voltage range | AC140–700V, three-phase; 50/60Hz |
| Overcurrent setting | 1–63A for the selected 63A rating |
| Overvoltage setting | 390–500V |
| Undervoltage setting | 260–370V |
| Voltage trip / restart delay | 0.1–30s / 1–500s |
| Voltage measurement accuracy | 2% |
| Output | 3NO internal relay contacts, original table |
| Insulation voltage | 700V for AC380V column |
| Protection / altitude | IP20; pollution degree3; ≤2,000m |
| Operating / storage ambient | −50°C to +55°C / −30°C to +70°C, original source |
| Dimensions | 90mm width × 95mm height; use complete original outline |
| Wiring | L1/L2/L3/N; input/output direction must follow the Product A/B drawing |
Selection and installation
This listing selects the three-phase AC380V line-to-line / 63A version. The original source also contains an AC220V L-N column; do not combine its 230–300V / 140–220V thresholds with this 380V version. Original instructions contain a single-phase application sentence copied into the three-phase section; the YC9VA-3 model, L1/L2/L3/N diagram and three-phase technical column control this listing. Factory photos identify YC9VA-3 and show the original terminal arrangement; follow the matching Product A/B input/output diagram. Voltage/current protection does not replace coordinated overload, short-circuit or residual-current protection.
Typical applications
Three-phase distribution and equipment supplies requiring monitored voltage/current limits and automatic restart delay.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.
Download the complete original CNC YC9VA-3 catalogue (PDF)
Download the complete original CNC YC9VA-3 instructions (PDF)