Product overview
The CNC Electric XJ3-D monitors a three-phase AC380V supply for overvoltage, undervoltage, phase failure and phase sequence error, opening its changeover control contact to release an external contactor.
Technical selection summary
| Manufacturer model | XJ3-D |
|---|---|
| Supply / frequency | AC380V, 50/60Hz |
| Overvoltage setting / delay | 380–460V / 1.5–4s, adjustable |
| Undervoltage setting / delay | 300–380V / 2–9s, adjustable |
| Phase failure / sequence response | ≤2s |
| Output contacts | 1CO changeover |
| AC-15 rated contact capacity | 0.47A at AC380V |
| Conventional thermal current Ith | 3A; separate from AC-15 Ie |
| Electrical / mechanical life | 100,000 / 1,000,000 operations |
| Operating ambient | −5°C to +40°C |
| Mounting | 35mm DIN rail or baseplate |
| Outline | 50mm maximum width × 106mm maximum height; original drawing for depth and holes |
Selection and installation
This is the CNC Electric XJ3-D AC380V version, separate from the existing CHINT XJ3 product. AC-15 contact capacity is 0.47A at 380V; Ith3A is a separate thermal rating, not the AC-15 capacity. The relay switches a contactor control circuit and is not a load breaker. Phase-failure coverage is limited to the monitored supply/terminals in the original circuit diagram; it does not prove protection against every downstream conductor fault.
Typical applications
Three-phase motor-contactor control circuits for pumps, compressors and machinery requiring phase-sequence and voltage monitoring.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.