The CHINT NQB1 combines an NS2 motor-protection unit, an NC1 AC contactor and a connecting module in one coordinated starter assembly. It provides direct starting and operational switching for three-phase squirrel-cage motors, with short-circuit, overload, phase-failure and temperature-compensation protection according to the selected rating.
Technical selection summary
| Manufacturer / series | CHINT NQB1-18 protective-starter family; illustrated NS2 / NC1 assembly |
|---|---|
| Starting duty | Direct-on-line starting and operational breaking of three-phase squirrel-cage induction motors |
| Main-circuit frequency | AC 50 Hz |
| Thermal-setting catalogue ranges | 0.1–0.16, 0.16–0.25, 0.25–0.4, 0.4–0.63, 0.63–1, 1–1.6, 1.6–2.5, 2.5–4, 4–6.3, 6–10, 9–14 and 13–18 A; select the exact range for the motor |
| Operating-voltage / current pairing | 380/400 V and 660/690 V catalogue duties depend on the rating row; the 18 A row is listed at 380/400 V, not at every family voltage |
| Illustrated 13–18 A range reference | 18 A version: 13–18 A thermal adjustment, 7.5 kW at 380/400 V in the manufacturer table |
| Contactor coil references | AC 110, 220 or 380 V, 50 Hz; coil supply is separate from main-circuit voltage |
| Construction suffixes | J0: economy without base; J1: economy with base; B0: standard construction |
| Short-circuit coordination | Conditional ratings require the exact specified SCPD/fuse and coordination combination; do not treat the family maximum as an unconditional breaking capacity |
| Insulation / impulse withstand | Rated insulation voltage 690 V; rated impulse withstand voltage 6 kV |
| Enclosure / installation | IP20; 35 mm DIN rail, incoming terminals upwards; mounting inclination within ±5° |
| Ambient / altitude | −5 to +40 °C, 24-hour average ≤+35 °C; altitude ≤2000 m |
| Standards reference | GB/T 14048.4 and IEC/EN 60947-4-1 |
Match the motor current, thermal-setting range, operating voltage, contactor coil and J0/J1/B0 construction together. The family limits of 18 A and 690 V do not establish an 18 A / 690 V combination. Use the manufacturer’s rating row and specified upstream short-circuit protection for the exact assembly.