CHINT · Residual current circuit breaker
Product overview
The CHINT NL1-63 Type AC / Type A provides residual-current protection for distribution circuits. It is an RCCB without integral overload or short-circuit protection; select the complete detection-type, sensitivity and pole code.
Technical selection summary
| Listing / poles | NL1-63 Type AC / Type A; 2P / 4P |
|---|---|
| Current selection | Manufacturer NL1-63 frame entries: 16, 25, 32, 40 or 63 A; match the chosen type and order row |
| Detection type | Type AC or Type A; Type A includes pulsating DC residual-current detection, while Type AC covers sinusoidal AC |
| Voltage / frequency | 2P order rows: AC 230/240 V; 4P order rows: AC 400/415 V; 50/60 Hz |
| Sensitivity | 30, 100 or 300 mA common order rows; other sensitivities and timed variants require their own exact code |
| Conditional short-circuit coordination | 6 / 10 kA versions are catalogue conditional Inc / IΔc ratings with the specified upstream SCPD; match the exact version |
| Mounting / standard | 35 mm DIN rail; IEC/EN 61008-1 manufacturer reference |
Choose instantaneous, G/SI or selective versions by the exact order code rather than combining their timing data. The RCCB needs coordinated overcurrent protection. Confirm the actual CE/UKCA or other destination documentation for the supplied version; this summary does not assert a certificate for every option.
Typical applications
- Residential and commercial distribution boards
- Industrial final distribution with coordinated residual-current protection
Product reference images and drawings
Match the exact model, suffix, electrical duty and mounting arrangement. The retained family references may show other versions; use the applicable manufacturer row and drawing for the ordered unit.