CHINT · Motor Protection Circuit Breaker
Product overview
CHINT 495081 is a three-pole NS2-25/1E motor protection circuit breaker with rocker controls. It provides overload, short-circuit and phase-loss protection for three-phase AC motors. The 6–10 A thermal setting is adjustable to suit the motor nameplate current. Red OFF and blue ON rocker controls provide local switching.
Technical selection summary
| Ordering code | 495081 |
|---|---|
| Manufacturer model | NS2-25/1E |
| Poles | 3P |
| Rated current (In) | 10 A |
| Current adjustment (Ir) | 6–10 A |
| Rated voltage | 230 / 400 / 690 V AC |
| Frequency | 50/60 Hz |
| Maximum operating voltage | 690 V AC |
| Insulation voltage (Ui) | 690 V AC |
| Impulse withstand voltage (Uimp) | 8 kV |
| Icu / Ics at 230/240 V AC | 100 / 100 kA |
| Icu / Ics at 400/415 V AC | Confirm against the nameplate of the supplied unit before selection. |
| Icu / Ics at 690 V AC | 3 / 2.25 kA |
| AC-3 motor power | 2.2 kW at 230 V, 4 kW at 400 V, 7.5 kW at 690 V |
| Control | Rocker ON/OFF |
| DIN width | 2.5 modules |
| Ingress protection | IP20 |
| Dimensions (H × W × D) | 91.3 × 44.5 × 80.8 mm |
| Ambient temperature | −5 to +40 °C |
| Maximum altitude | 2,000 m |
| Mounting inclination | Within ±5° of the specified mounting plane |
| Reference standard | IEC/EN 60947-2 |
| Units per pack / carton | 1 / 60 |
| EAN | 6925808307899 |
| Average ambient temperature over 24 hours | ≤35 °C |
| Relative humidity | ≤50% at 40 °C or up to 90% at 20 °C |
| Pollution degree / installation category | 3 / II, III |
| Terminal screw / tightening torque | M4 / 1.7 N·m |
| Conductor strip length | 10 mm |
| Switching frequency | ≤30 operations per hour |
Short-circuit ratings by operating voltage
| Voltage | Icu | Ics |
|---|---|---|
| 230/240 V AC | 100 kA | 100 kA |
| 400/415 V AC | Confirm the supplied unit’s nameplate before selection. | |
| 500 V AC | 10 kA | 7.5 kA |
| 690 V AC | 3 kA | 2.25 kA |
The 230/240 V, 500 V and 690 V values above refer to the nameplate shown in the product gallery. The 400/415 V rating requires confirmation for the supplied unit.
Motor selection
Set the thermal adjustment using the motor nameplate current within the 6–10 A range. The AC-3 power ratings in the table are voltage-specific.
Typical applications
- Machine motor feeders
- Three-phase pump and fan protection
- Manual motor control panels