NOARK · B1
Product overview
Original NOARK B1H, B1N and B1D branch-circuit miniature breakers. Choose the exact family, pole and rated-voltage version; only supported currents and curves remain available.
Technical selection summary
| Parameter | Specification |
|---|---|
| B1H | 0.5-32A; 1P277VAC; 2P/3P480Y/277VAC; B/C/D curves |
| B1N | 0.5-63A; 1P/2P/3PAC240V; 1PDC60V or2PDC125V; B/C/D curves |
| B1D | 0.5-63A; 1PDC125V or2PDC250V; C/D curves only |
| UL489 interrupting | 10kA at the exact version voltage, not a universal 480VAC straight-delta rating |
| Instantaneous ranges | B1H/B1N:B3-5In, C5-10In, D10-20In; B1D:C7-15In, D12-22In |
| Terminals / mounting | Publishedbox-lug terminal version; 35mmDINrail; ring-tongueRsuffix is a separate option not selected here |
| Standards | Original manufacturer UL489/CSAC22.2No.5 fileE355392; IECratings are separately stated in retained source |
| Environment / wiring | Use the full manufacturer wiring, temperature/elevation derating, curves and dimensional pages below |
B1D is DC only and has no3P/B curve selection; B1H is limited to 32A and 480Y/277V grounded-wye conditions. B1E4P and B1NQ are separate products. Do not apply UL10kA and IECIcu/Ics interchangeably.
Typical applications
- Electrical distribution and motor control