DELIXI ELECTRIC · High-current AC circuit breaker
Product overview
DELIXI CDB6i-125 provides overload and short-circuit protection for higher-current distribution circuits. Select the complete 63–125 A model, pole arrangement and C/D trip characteristic.
Technical selection summary
| Series / frame | DELIXI CDB6i-125, high-current frame |
|---|---|
| Rated current choices | 63, 80, 100 or 125 A |
| Pole choices | 1P, 1P+N, 2P, 3P, 3P+N or 4P |
| AC operating-voltage reference | 1P / 1P+N: 230/240 V AC; 2P / 3P / 3P+N / 4P: 400/415 V AC in the linked three-page catalogue. |
| Trip-characteristic selection | C or D thermal-magnetic trip; B belongs to the separate legacy standard-CDB6i reference. |
| Manufacturer breaking-capacity reference | 10 kA headline in the CDB6i-125 catalogue. The technical table labels this Icn under IEC/EN 60898-1, while the overview names GB/T 14048.2 / IEC 60947-2. Confirm the exact marked standard and test documentation for the supplied version. |
| Standard CDB6i — Product Name | CDB6i Miniature Circuit breaker |
| Standard CDB6i — Brand | DELIXI ELECTRIC |
| Standard CDB6i — Pole Number | 1P, 1P+N, 2P, 3P, 3P+N, 4P |
| Standard CDB6i — Rated current | 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
| Standard CDB6i — Volatge | 1P 230/400V AC 1P+N 230V AC 2P, 3P, 3P+N, 4P 400V AC |
| Standard CDB6i — Breaking Capacity | 6kA |
| Standard CDB6i — Trip curve | B, C, D |
| Standard CDB6i — Operating temperature | -35℃~70℃ |
| Rated frequency reference | 50/60 Hz AC in the DELIXI CDB6i-125 manufacturer table. Match the complete model, rated current, pole arrangement and actual unit marking |
| Manufacturer protection-function reference | Thermal-magnetic trip in the DELIXI CDB6i-125 manufacturer table. This is the 63–125 A family reference; the separate 1–63 A CDB6i legacy table is a separate range |
| Earlier comparative catalogue — CDB6i-125 AC voltage | In the DELIXI 63–125 A CDB6i-125 table: 1P and 1P+N are listed at 230/240 V AC; 2P, 3P, 3P+N and 4P at 400/415 V AC, with a separate 2P 230/240 V AC entry. Match the complete pole/voltage version. These are CDB6i-125 references, not ratings taken from the separate 1–63 A legacy table |
The rows marked Standard CDB6i describe the separate 1–63 A comparison; their 6 kA and B/C/D data do not rate a CDB6i-125. The earlier comparative catalogue also lists a separate 2P 230/240 V AC entry; the linked three-page edition lists 2P at 400/415 V AC. Match the actual marked version. The PDF also contains DC data; it does not expand this AC listing.
Typical applications
- Higher-current AC distribution circuits.
- Panel assemblies matched to the exact current, poles and characteristic.