NewTrend · PV DC Isolation
Product overview
The YSS UL508i-version family is a compact non-polar DC disconnect switch for solar inverter DC circuits, independent MPPT inputs and battery energy-storage applications. This page offers the documented 1500 V DC, 13 A-per-conductor version, with 2P, 4P, 6P or 8P construction and panel or DIN-rail mounting.
Key features
- 1500 V DC / 13 A per conductor; two poles in series per string.
- One to four independent strings, according to 2P / 4P / 6P / 8P construction.
- Non-polar switching and lockable standard black handle.
- Documented arc-extinguishing reference: 3 ms.
- 10000 mechanical and 6000 electrical operations.
- Panel and DIN-rail versions with complete wiring and installation drawings.
Model and mounting selection
| Model | Poles | Mounting | Independent strings |
|---|---|---|---|
| YSS.1-50/T-2-1500V | 2P | Panel | 1 |
| YSS.1-50/T-4-1500V | 4P | Panel | 2 |
| YSS.1-50/T-6-1500V | 6P | Panel | 3 |
| YSS.1-50/T-8-1500V | 8P | Panel | 4 |
| YSS.2-50-2-1500V | 2P | DIN rail | 1 |
| YSS.2-50-4-1500V | 4P | DIN rail | 2 |
| YSS.2-50-6-1500V | 6P | DIN rail | 3 |
| YSS.2-50-8-1500V | 8P | DIN rail | 4 |
Electrical characteristics — 1500 V / 13 A version
| Standard reference | UL508i |
|---|---|
| Operational voltage / current | 1500 V DC / 13 A per conductor |
| Poles in series | 2 per string |
| Rated impulse withstand voltage, Uimp | 8 kV |
| Short-time withstand current, Icw | 1.5 kA, 1 s |
| Short-circuit making capacity, Icm | 2.0 kA |
| Standard short-circuit rating | 5 kA |
| High-fault short-circuit rating | 8 kA |
| Electrical endurance | 6000 operations |
| Mechanical endurance | 10000 operations |
| Ambient temperature | −40 °C to +85 °C |
| Storage temperature | −40 °C to +85 °C |
| Relative humidity | 90% |
| Pollution degree | 2 |
| Protection reference | ≥IP66 / Type 4X as stated in this document section; assembled installation and supplied-product applicability: To be confirmed |
| Factory listing reference | UL508i, E482690 in original document; applicability and markings of the supplied OEM product: To be confirmed |
Installation and conductors
| Terminal screws | M4, 1.2–1.8 N·m |
|---|---|
| Panel mounting nut | 2.0–2.5 N·m |
| Standard black knob screw | M3, 0.5–0.7 N·m |
| Extension-rod knob screw | M3, 1.5–1.8 N·m |
| Panel thickness | 1.5–3 mm |
| Conductor | Copper; one wire per pole |
| Wire size reference | 12–6 AWG / 2.5–16 mm² |
| Wiring-table torque reference | 1.8 N·m |
| Panel cutout | 12.0 mm nominal flat / 16.0 mm nominal overall cutout, with original tolerances retained in drawing |
| Panel-body reference | 47.0 mm width, 60.0 mm height, 45.0 mm nominal depth; use complete drawing and tolerances |
| DIN-body reference | 47.0 mm width, 78.0 mm overall mounting height; 68.0 mm fixing centres and Ø4.5 mm fixing reference |
Layer-dependent lengths and all tolerances remain in the complete dimension drawings. Handle position, panel gasket, OFF/ON markings, wiring entry direction and mounting details are retained. Follow the diagram applicable to the exact supplied mounting version.
Handle and additional family references
The standard black handle is the selectable version illustrated by the current factory-page photographs. The separate S-type extension handle is a YSS.2 reference; supplied assembly compatibility: To be confirmed. The document gives extension-height ranges of 130–280 mm (2P), 150–300 mm (4P), 170–320 mm (6P) and 190–340 mm (8P).
The full document also includes lower-voltage YSS-50 and YSS-63F auxiliary-signal versions. Their ratings are separate reference sections and are not applied to the selectable 1500 V / 13 A version.
| Lower-voltage 50-frame reference | 350/500/600 V: 16/18/20/25/32/38/40/45/50 A; 750 V: 50 A; 1000 V: 16/22/25/30 A, according to the original table grouping |
|---|---|
| 63F voltage/current reference | 1000 V / 50 A; 1300 V / 40 A; 1500 V / 25 A |
| 63F separate thermal/insulation references | Ith 63 A; Ui 1500 V; Uimp 8 kV |
| 63F short-circuit references | Icw 1.0 kA / 1 s; Icm 1.5 kA; conditional short-circuit current 8 kA |
| 63F operation and environment | 6000 electrical / 10000 mechanical operations; 120/h; −40..+70 °C ambient and storage, 90% RH, pollution degree 2 |
| 63F installation references | IP20 terminals / IP66 panel; 14–8 AWG stranded or 2.5–10.0 mm²; separate 150 mm signal-wire drawing |
| 63F auxiliary microswitch | Normally open; DC 48 V 0.1 A / DC 12 V 0.3 A / AC 125–250 V 0.1 A; mechanical 60/min, electrical 20/min; mechanical ≥500000 and electrical ≥100000; AC 600 V, 50/60 Hz, 1 min between terminals; IP67 |
| Additional version supply | To be confirmed; reference sections retained without unverified selectable combinations |
Complete family technical document
Download the complete six-spread / twelve-printed-page YSS UL family datasheet
The complete original layout retains the lower-voltage, 1500 V / 13 A and 63F sections, all current tables, switching configurations, wiring diagrams, dimensions and handle references.