NewTrend · PID temperature control
Product overview
The OTC series provides PID or ON/OFF temperature control with a 100ms sampling period, a dual PV/SV display and front-button settings. Relay and SSR-drive output functions support different heating-control arrangements. Four panel sizes provide compact square or vertical-format options for process equipment and control cabinets.
Technical selection summary
| Models | OTC4S / OTC4M / OTC4L / OTC4H |
|---|---|
| Supply | 100–240V AC, 50/60Hz |
| Sampling period | 100ms |
| Accuracy | ±0.5%FS ±1°C |
| Control method | PID or ON/OFF |
| Control outputs | Electromagnetic relay and SSR drive output; configure to suit the load circuit |
| Input types | Thermocouple / RTD inputs; K, J, E, S, R, B, N, T, Pt100 and Cu50 listed for the series |
| Display | Dual four-digit PV / SV display with LED status indicators |
| Settings | Front push buttons |
| Power consumption | Less than 10VA |
| Operating temperature | −10°C to +50°C |
| Operating humidity | 35–85% RH, non-condensing |
| Housing depth | 75mm |
| Mounting | Panel mounting with retaining clips |
Panel size and mounting selection
| Model | Panel W × H | Panel cut-out W × H |
|---|---|---|
| OTC4S | 48 × 48mm | 45 × 45mm |
| OTC4M | 72 × 72mm | 68 × 68mm |
| OTC4L | 96 × 96mm | 92 × 92mm |
| OTC4H | 48 × 96mm | 45 × 92mm |
OTC4S dimensions
The OTC4S uses a 48 × 48mm panel face and a 45 × 45mm cut-out, with a 75mm body-depth reference. Leave rear clearance for the terminal connections and mounting clip.
OTC4M dimensions
The OTC4M uses a 72 × 72mm panel face and a 68 × 68mm cut-out, with a 75mm body-depth reference. Leave rear clearance for the terminal connections and mounting clip.
OTC4L dimensions
The OTC4L uses a 96 × 96mm panel face and a 92 × 92mm cut-out, with a 75mm body-depth reference. Leave rear clearance for the terminal connections and mounting clip.
OTC4H dimensions
The OTC4H uses a 48 × 96mm panel face and a 45 × 92mm cut-out, with a 75mm body-depth reference. Leave rear clearance for the terminal connections and mounting clip.
PID, ON/OFF and output configuration
The controller supports PID regulation or ON/OFF switching. The relay output and SSR-drive function provide different interfaces to the load circuit. An SSR drive signal operates a suitable external solid-state relay; it does not directly power the heater. Match the configured input type to the installed sensor and use the terminal arrangement for the selected housing.
OTC4S terminal wiring
The diagram illustrates the AC supply, heater circuit and thermocouple or Pt100 sensor connections for the OTC4S. Terminal layouts differ between housing sizes. Isolate the supply before wiring and follow the terminal identification on the supplied controller.
OTC4M terminal wiring
The diagram illustrates the AC supply, heater circuit and thermocouple or Pt100 sensor connections for the OTC4M. Terminal layouts differ between housing sizes. Isolate the supply before wiring and follow the terminal identification on the supplied controller.
OTC4L terminal wiring
The diagram illustrates the AC supply, heater circuit and thermocouple or Pt100 sensor connections for the OTC4L. Terminal layouts differ between housing sizes. Isolate the supply before wiring and follow the terminal identification on the supplied controller.
OTC4H terminal wiring
The diagram illustrates the AC supply, heater circuit and thermocouple or Pt100 sensor connections for the OTC4H. Terminal layouts differ between housing sizes. Isolate the supply before wiring and follow the terminal identification on the supplied controller.
Display, installation and applications
The red PV and green SV readings allow the measured value and set value to be checked together. LED indicators show operating status, while the front keys provide local setting access. Suitable applications include temperature-regulated machinery, heating processes and industrial control panels. Keep the controller within its specified ambient temperature and non-condensing humidity range, and provide suitable protection for the complete installed assembly.