NewTrend · PV Rapid Shutdown
Product overview
FS-A1 is an aluminum-enclosed single-input module-level rapid shutdown device with monitoring capability. It supports emergency-button shutdown, shutdown on AC power loss at associated equipment and automatic overtemperature shutdown above 100°C. Select the verified input-voltage/current/power configuration below.
Protection and operation
The aluminum enclosure supports heat dissipation. Emergency-button operation and loss of the associated AC supply initiate shutdown. Compatible monitoring equipment is required to display temperature, voltage, current and device status; it is a separate system component.
Technical selection summary
Product identity
| Model | FS-A1 |
|---|---|
| Version | Monitoring version with aluminum enclosure |
| PV input configuration | One input |
| Application | Module-level PV rapid shutdown |
| Standards | EN 62109-1:2010; EN 61058-1:2018 |
Verified input configurations
| 110V input version | 110V; 20A; 2200W |
|---|---|
| 70V input version | 70V; 25A; 1750W |
| Input / current / power correspondence | The selected voltage, current and maximum power form one configuration; ratings are not interchangeable between versions |
PV cables and connectors
| PV input and output cables | 4.0mm² (12AWG) cables with MC4 connectors |
|---|---|
| PV input cable length | 180mm |
| PV output cable length | 1800mm |
| PV connector rating | 1500V MC4 connector |
RSD auxiliary DC power and signalling
| Supply voltage range | 14–28V DC |
|---|---|
| Maximum auxiliary current | 15mA |
| Maximum auxiliary power | 0.2W |
| Power / signal cables | 2 × 0.823mm² (18AWG) signal cables with signal connectors |
| Signal cable length | 1800mm |
| Monitoring method | POWERBUS; compatible monitoring equipment is required for monitoring functions |
Protection and installation
| Enclosure material | Aluminum |
|---|---|
| Degree of protection | IP68 |
| Operating temperature | −40°C to +85°C |
| Storage temperature | −40°C to +85°C |
| Automatic overtemperature shutdown | Internal temperature >100°C |
| Manual shutdown | Emergency button switch |
| Automatic supply-loss shutdown | AC supply loss at the associated switch/monitoring equipment |
| Shutdown operating principle | Panels shut down to 0V at microsecond scale as described by the source |
| Overall dimensions | 118 × 107 × 28.4mm |
| Drawing tolerances | 118 ±1 × 107 ±1.5 × 28.4 ±1mm |
System integration reference
| General inverter / panel compatibility | Compatible with most string inverters and panels; no cross-talk with inverter or Wi-Fi according to the source |
|---|---|
| Example installation | 2-to-1 arrangement: four panels and two FS-A1 devices |
| NEC2017 / NEC2020 source recommendation | One panel with panel voltage ≥40V, or two panels with panel voltage <40V per FS-A1 |
| Monitoring equipment reference | FS-MH-01-N (100–240V AC) / FS-MH-02-N (200–480V AC), supplied separately |
| Monitoring-device enclosure dimensions | To be confirmed by channel version; source reference table and one-channel drawing differ |
Documentation for supplied product
| Certification applicability | To be confirmed for the supplied product marking |
|---|---|
| Warranty terms | To be confirmed for supplied product; source product lists 10 years |
System wiring example
Four panels with two FS-A1 units. Panel count must follow the applicable voltage conditions and local installation requirements.
Shutdown modes
Installation dimensions
FS-A1 / FS-A2 family and separate monitoring-device reference drawings. Dimensions in mm; monitoring-device dimensions require confirmation by channel version.
Download the complete FS-A1/A2 monitoring family datasheet (6 pages)
Reference installations
Illustrative application references from the original product documentation; these are not represented as NewTrend project supply.